BLD-Aging Inspection | 6/25/2020 | 6/25/2020 | 6/25/2020 | | PASS |
Jim Storey
|
|
|
|
BLD-Aging Inspection | 6/24/2020 | 6/24/2020 | 6/24/2020 | | DEFR |
Jim Storey
|
|
|
475 According to city approved drawings the new the new HVAC roof top untis are 3900 CFM each, HVAC units that are more than 2000 CFM requires unit shutdown on in-duct smoke detector activation. A seperate FIR perit will be required for any and all additions/modifications to the fire alarm system, no other items have been inspected.
|
FIRE-Final Inspection | 2/10/2020 | 2/11/2020 | 2/11/2020 | A | FAIL |
Jim Page
|
|
|
According to city approved drawings the new the new HVAC roof top untis are 3900 CFM each, HVAC units that are more than 2000 CFM requires unit shutdown on in-duct smoke detector activation. A seperate FIR perit will be required for any and all additions/modifications to the fire alarm system, no other items have been inspected.
Mike Phone #: ###-####
|
Override - Parcel Holds | 1/10/2020 | 1/1/1900 | 1/10/2020 | | |
|
|
|
override
|
Issue PAID IN FULL permit | | | 8/20/2019 | | DONE |
|
|
|
|
Telephone call | | | 8/19/2019 | | DONE |
|
|
|
Emailed Zach and Kevin to inform them the fire fee was missed and once that remaining fee is paid for they can pick up their paper plans.
|
Plan assigned to (M_H) | 7/24/2019 | | 7/29/2019 | | DONE |
Michael Hanson
|
|
|
07/29 #518 L2 Paper - CSB Warehouse
|
1st review completed | | | 7/29/2019 | | DONE |
Michael Hanson
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/29/2019 | | DONE |
Michael Hanson
|
|
|
|
Case Summary (BLD) | | | 7/29/2019 | | DONE |
Michael Hanson
|
|
|
|
Print Occupancy Form | | | 7/29/2019 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/29/2019 | | DONE |
|
|
|
MET JOSH.KINCAID@STEEDCONSTRUCTION.COM
Need
GC Form
Revised Cert of Value
|
Telephone call | | | 7/29/2019 | | DONE |
|
|
|
Spoke with Randy informing him that this permit is ready and we will need the 302 & 306 filled out by the GC for us to put the rest of the fees in. Stated he will informed steed construction
|
Routing - PLAN CHECK | 7/16/2019 | | 7/29/2019 | | PASS |
Michael Hanson
|
|
|
|
Routing - FIRE | 7/16/2019 | 7/16/2019 | 7/25/2019 | | PASS |
Mark Scharfen
|
|
|
07.25.2019-Completed fire review. Made notations on plans. Racking changes require additional permit. MS
|
Plan assigned to (CJW) | 7/16/2019 | | 7/24/2019 | | DEFR |
Carl Westfall
|
|
|
minor - paper - 7-23-19
|
Plan Reviewer's activity | | | 7/16/2019 | | PASS |
|
|
|
Plan intake review approved
|
Plans ACCEPTED BY PLAN TECH | | | 7/16/2019 | | DONE |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/16/2019 | | DONE |
|
|
|
|
Intake Approval | | | 7/16/2019 | | PASS |
|
|
|
|
Application received | | 7/16/2019 | | | |
|
|
|
|