Second Notice | | 7/19/2020 | 7/27/2020 | | DONE |
|
|
|
This permit finaled on the web by Charlene Meadows
|
First Notice | | 5/10/2020 | 7/9/2020 | | DONE |
|
|
|
mailed 7-9-2020
|
Permanent Occupancy | | | 4/30/2020 | | DONE |
|
|
|
|
BLD-Final | 4/22/2020 | 4/22/2020 | 4/22/2020 | P | PASS |
Dave Hannah
|
|
|
Please contact Jim Hibbard 30 minutes prior to arrival Phone #: ###-#### Inspection requested via web by James Hibbard
|
FIRE-Final Inspection | 4/16/2020 | 4/17/2020 | 4/17/2020 | P | PASS |
Jim Page
|
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work is complete.
Please contact Jim 30 minutes prior to arrival Phone #: ###-#### Inspection requested via web by James Hibbard
|
CHANGE STATUS TO (ISS) | | | 3/30/2020 | | DONE |
|
|
|
plan mod
|
Routing - PLAN CHECK | 3/18/2020 | | 3/20/2020 | | PASS |
Carl D Madsen
|
|
|
|
Permit Ready to Issue | | | 3/20/2020 | | DONE |
|
|
|
plan mod met
|
Routing - MECHANICAL | 3/18/2020 | | 3/19/2020 | | PASS |
Troy James
|
|
|
|
Plan assigned to (CDM) | 3/5/2020 | 3/5/2020 | 3/5/2020 | | |
Carl D Madsen
|
|
|
plan mod #1 inspector has asked that inforation ber revised showing correct location of existing fire dampers
|
Plan Modification Accepted | | | 3/5/2020 | | DONE |
|
|
|
plan mod #1
|
BLD-Ceiling Grid Inspection | 2/25/2020 | 2/26/2020 | 2/26/2020 | P | PASS |
Dave Hannah
|
|
|
Please contact Jim 30 minutes prior to arival Phone #: ###-#### Inspection requested via web by James Hibbard
|
BLD-Framing/Rough-in | 12/20/2019 | 12/20/2019 | 12/23/2019 | P | PASS |
Dave Hannah
|
|
|
Please contact Jim 30 minutes before arriving Phone #: ###-#### Inspection requested via web by James Hibbard sub floor framing for plateforms
|
BLD-Framing/Rough-in | 12/10/2019 | 12/10/2019 | 12/10/2019 | P | PART |
Dave Hannah
|
|
|
please call 30 minutes pryor to arival Phone #: ###-#### Inspection requested via web by James Hibbard ok to cover walls
|
BLD-Framing/Rough-in | 12/3/2019 | 12/4/2019 | 12/4/2019 | P | PART |
Tony Young
|
|
|
Please contact Jim Hibbard 30 minutes before arriving thanks Phone #: ###-#### Inspection requested via web by James Hibbard,, ok to one side walls
|
Print Occupancy Form | | | 11/22/2019 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 9/18/2019 | | DONE |
|
|
|
|
Route to Impact Fee Review | 9/4/2019 | 9/7/2019 | 9/6/2019 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Plan assigned to (CDM) | 8/28/2019 | 8/28/2019 | 9/5/2019 | | PASS |
Carl D Madsen
|
|
|
|
Plan resubmittals received | | | 9/5/2019 | | DONE |
Joe Bruce
|
|
|
|
Routing - PLAN CHECK | 9/5/2019 | | 9/5/2019 | | PASS |
Joe Bruce
|
|
|
ALS system located on sheet AV-121 and AV-401. **JHB**
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/5/2019 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/5/2019 | | DONE |
|
|
|
MET BRANDON@EKCCONSTRUCTION.COM
NEED
GC FORM
REVISED VALUE
|
Routing - FIRE | 8/12/2019 | 8/12/2019 | 9/4/2019 | | PASS |
Mark Scharfen
|
|
|
09/04 Ada County Courthouse review complete. Uploaded rev_fire 09.04.2019.pdf
|
1st review completed | | | 9/4/2019 | | FAIL |
Carl D Madsen
|
|
|
|
Plan resubmittals requested | | | 9/4/2019 | | DONE |
Joe Bruce
|
|
|
Sent ePlan task back to applicant for resubmittal. **JHB**
|
Plan assigned to (CJW) | 8/12/2019 | 9/5/2019 | 8/28/2019 | | DEFR |
Carl Westfall
|
|
|
08/29/19 (L-3 - 15 days) (eplan - 40 sheets) ADA County Courthouse
|
Routing - PLAN CHECK | 8/12/2019 | | 8/28/2019 | | FAIL |
Carl D Madsen
|
|
|
|
Routing - Addressing | 8/12/2019 | | 8/14/2019 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 8/12/2019 | | 8/13/2019 | | PASS |
Morgan Webb
|
|
|
|
Routing - MECHANICAL | 8/12/2019 | | 8/13/2019 | | PASS |
Troy James
|
|
|
|
Routing - PLUMBING | 8/12/2019 | | 8/13/2019 | | PASS |
Daryl Spivey
|
|
|
per plan and ISPC.
|
Intake Approval | | | 8/9/2019 | | PASS |
|
|
|
|
Intake Approval | | | 8/5/2019 | | FAIL |
Javier Guzman
|
|
|
Provide and upload the following:
• The court room is an assembly space and will be processed as a Major T.I., provide a completed 520 checklist and upload any additional items requested from the 520 checklist.
• All mechanical and plumbing sheets are uploaded in the vertical position and are required to be uploaded in Landscape format in the horizontal position per ePlan submittal standards.
|
Application received | | | 7/31/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 31 2019 4:39PM
|