Final | 3/12/2020 | 3/13/2020 | 3/13/2020 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Corrections made final ok
|
Final | 3/4/2020 | 3/5/2020 | 3/5/2020 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud 110.3 GFCI Hot grnd revers Elevator pit. GFCI dead SE Stair well door Exterior. Wall pack needs installed/repaired above main service. Pig tail needs install for sprinkler time clock. 440.24 Max overcurrent for 4 RTU's is 40A 45A installed. 330. MC Stapped Less than 1 1/4in from face of stud misc areas on exterior walls
|
Permanent Service | 1/23/2020 | 1/24/2020 | 1/24/2020 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud p/s u/g n ok
|
Electrical Rough-In | 11/26/2019 | 11/27/2019 | 11/27/2019 | A | PASS |
Rock A. Hudson
|
|
|
Matt Garcia ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud Riser room switch wall, south wall pack, up parapet receptacles in walls rough in ok cover
|
Electrical Rough-In | 10/3/2019 | 10/4/2019 | 10/4/2019 | P | PASS |
James Ady
|
|
|
Inspect underground to backfill. Matt Garcia ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud 1in to monument sign, 3in from mech room to service and L.V sleaves to elevator shaft ok to cover
|
Electrical Rough-In | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground from transformer to building only ok to cover
|
Electrical Rough-In | 9/30/2019 | 10/1/2019 | 9/30/2019 | P | CANC |
James Ady
|
|
|
Underground to cover Phone #: ###-#### >> Inspection requested via web by Jeremy Cloud Inspection cancelled from web by: Jeremy Cloud
|
Electrical Rough-In | 9/25/2019 | 9/25/2019 | 9/25/2019 | P | PASS |
James Ady
|
|
|
Inspect Ufer Phone #: ###-#### Inspection requested via web by Jeremy Cloud UFER only ok to cover
|
Electrical Rough-In | 9/18/2019 | 9/19/2019 | 9/19/2019 | P | PASS |
James Ady
|
|
|
Maz Phone #: ###-#### Underground to light pole and pole bases ok to cover
|
Issue PAID IN FULL permit | | | 9/17/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/17/2019 | | DONE |
|
|
|
This permit was created on the web by Jeremy Cloud
|
First Notice | 3/13/2020 | 3/13/2020 | | | |
James Ady
|
|
|
|