Final | 2/5/2020 | 2/5/2020 | 2/5/2020 | P | PASS |
Tom Saunders
|
|
|
All issues fixed. Phone #: ###-#### Inspection requested via web by Dan Jennings... corrections made...ok to final
|
Final | 2/3/2020 | 2/4/2020 | 2/4/2020 | A | FAIL |
Tom Saunders
|
|
|
Final inspection for Encore Townhomes. The garage door code is 6622, Please let me know if you have any question! Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings..... 1) all exterior recepticles shall be rated weather resistant...406.9 2) plate for outlet under sink shall be rated to be used with handy box...110.3, 406.6 3) a recepticle shall be within 3ft of edge of each sink in master bathroom...210.52(D)
|
Electrical Rough-In | 10/10/2019 | 10/10/2019 | 10/10/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Jennings...rough in ok to cover... intersystem bond needs installed-check at final.. discussed with contractor the combination of inspection types R, RP/S, P/S
|
Permanent Service | 10/10/2019 | 10/10/2019 | 10/10/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Jennings... p/s u/g new ok
|
Issue PAID IN FULL permit | | | 10/10/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/30/2019 | | DONE |
|
|
|
This permit was created on the web by Dan Jennings
|