Final | 4/7/2020 | 4/7/2020 | 4/7/2020 | P | PASS |
Rock A. Hudson
|
|
|
Final please. Thank you. Phone #: ###-#### Inspection requested via web by Kyle Lott Final ok
|
Final | 4/3/2020 | 4/6/2020 | 4/6/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Final inspection Please. Have a bless week. Phone #: ###-#### Inspection requested via web by Kyle Lott 110.12(A)- Unused openings shall be closed by approved means. Ceiling bell boxes have open knock outs. 110.22- Required structure disconnecting means shall be labeled. 225.32- Required structure disconnecting means shall be installed in a readily accessible location. Mounted at same height as exit signs. BCC 4-05-23- Unlawful to cover in any way electrical installation. Must expose 2 locations of underground conduit to bike enclosure to verify depth.
|
ELE-Request for Extension | 4/1/2020 | 4/1/2020 | 4/1/2020 | P | PASS |
Rock A. Hudson
|
|
|
NOT AN INSPECTION REQUEST BUT A REQUEST TO EXTEND THIS PERMIT PLEASE. THIS PERMIT EXPIRES ON 4/6/2020 - PLEASE EXTEND. CALL MARIA FOR ANY QUESTION. ###-#### Phone #: ###-#### Inspection requested via web by Kyle Lott Extension ok
|
Final | 3/24/2020 | 3/25/2020 | 3/25/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Final inspection please. Thank you. Have a bless day! Phone #: ###-#### Inspection requested via web by Kyle Lott 110.12(A)- Unused openings shall be closed by approved means. KOs in bell boxes in ceiling. 225.32- Seperate structures shall have a disconnecting means. 342.30- IMC shall be secured with in 3' of emerging from grade. BCC 4-05-23- Underground to bike structure did not have an inspection.
|
Issue PAID IN FULL permit | | | 10/9/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/9/2019 | | DONE |
|
|
|
This permit was created on the web by Kyle Lott
|
First Notice | 4/7/2020 | 4/7/2020 | | | |
Rock A. Hudson
|
|
|
|