First Notice | 5/8/2020 | 5/8/2020 | 6/9/2020 | | DONE |
Tom Saunders
|
|
|
This permit finaled on the web by Scott Campbell
|
Final | 5/7/2020 | 5/8/2020 | 5/8/2020 | A | PASS |
Tom Saunders
|
|
|
call for access - screened // Carl Phone #: ###-####...ok to final
|
Final | 4/30/2020 | 5/4/2020 | 5/4/2020 | A | FAIL |
Tom Saunders
|
|
|
Screened-please call for access building is vacant- Darin Phone #: ###-####... 1) work not complete...receptacles shall be installed completely 2) receptacles need installed firmly againstfinished surface with plates installed...406.5 2nd attempt at final..further fails will result in reinspection fees
|
Final | 3/18/2020 | 3/19/2020 | 3/19/2020 | A | NH |
Tom Saunders
|
|
|
Contact Ryan Wiedrich Phone #: ###-#### Inspection requested via web by Scott Campbell.. no access closed because of safety from virus
|
Final | 3/13/2020 | 3/13/2020 | 3/13/2020 | P | FAIL |
Tom Saunders
|
|
|
Contact Julian Lopez (General Contractor) for access. Phone #: ###-#### Inspection requested via web by Scott Campbell... 1) receptacles shall be firmly fastened to wall 2) all receptacles and switches shall have platesinstalled 3) work shall be completed before scheduling final inspections
|
Electrical Rough-In | 2/25/2020 | 2/26/2020 | 2/26/2020 | P | PASS |
Tom Saunders
|
|
|
Contact is Darrin Phone #: ###-#### Inspection requested via web by Scott Campbell...open walls ok to cover...rerouting breakroom circuits and fished in outlets at coffee bar and in breakroom
|
Issue PAID IN FULL permit | | | 2/25/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/25/2020 | | DONE |
|
|
|
This permit was created on the web by Scott Campbell
|