Electrical Rough-In | 7/10/2020 | 7/13/2020 | 7/13/2020 | A | CANC |
Rock A. Hudson
|
|
|
All set have a good day Phone #: ###-#### Inspection requested via web by TRENT Swaim Inspected 7-10-20. Duplicate request.
|
Electrical Rough-In | 7/10/2020 | 7/10/2020 | 7/10/2020 | P | PASS |
Rock A. Hudson
|
|
|
Basement west wall has conduits with wiring out of conduit. All must be removed or terminate in a box as per 300.15. 6 circuits provided for show window receptacles Main level only rough in ok cover
|
Rough-In Permanent Service | 7/8/2020 | 7/9/2020 | 7/9/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Please call me before you head down, have a great day. Can be a.m. if necessary. Phone #: ###-#### Inspection requested via web by TRENT Swaim City approved set of prints on site confirmed. Basement to remain unfinished. Daylite responsive control noted on print. 110.12(B)- Existing electrical boxes in basement shall not be damaged. Bent, loose, not secured. 110.24- Available fault current shall be posted prior to approving permanent service. 210.62- Show window receptacles shall be installed for all major fraction of 12' of show window space. 6' of window and area above front door. 220.14(G)- Branch circuit calculation for show window lengths of 22', 24, and 6'= 10.4 kw. A minimum of 5 20 amp 120 volt circuit for show window receptacles. 250.24(A)(1)- Grounding electrode conductor shall terminate and same bus or terminal as grounded conductor in right panel. 300.4- MC cable shall be protected form damage where run thru notched wood by nail plates. Basement beans and upstairs above door. 314.23- Boxes shall be securely mounted in place. Up west wall and basement existing boxes 330.30- MC shall be secured with in 12" of a box. Level 1 east wall and few lights. 408.7- Unused breaker space shall be closed by approved means.
|
Issue PAID IN FULL permit | | | 7/7/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/7/2020 | | DONE |
|
|
|
This permit was created on the web by TRENT Swaim
|