Electrical Rough-In | 8/5/2020 | 8/5/2020 | 8/5/2020 | P | PASS |
Eric Story
|
|
|
Corrections fixed- Wall only ok to cover
|
Electrical Rough-In | 8/5/2020 | 8/5/2020 | 8/5/2020 | P | FAIL |
Eric Story
|
|
|
Code 9481. Walls only Phone #: ###-#### Inspection requested via web by Dave Brueggemann Corrections not fixed MC not replaced as MARKED on metal stud on previous inspection-If not fixed re-inspection fee to be added
|
Electrical Rough-In | 8/3/2020 | 8/4/2020 | 8/4/2020 | A | FAIL |
James Ady
|
|
|
walls only Phone #: ###-#### Inspection requested via web by Dave Brueggemann 11o.3B Insulated bushings shall be installed on MC a per instructions. 330.24 MC Bent to breaking point(Next to back door.) 300.4 MC shall not be secured within 1 1/4in from face of framing(Water heater and recep back office) 110.12 Opening shall be closed(Missing conduit or KO seal Hall 4 gang.) MC not completed to floor box junction point.
|
Electrical Rough-In | 7/20/2020 | 7/21/2020 | 7/21/2020 | A | PASS |
Rock A. Hudson
|
|
|
Underground only Phone #: ###-#### Inspection requested via web by Dave Brueggemann City approved set pf prints on site confirmed. Under slab rough in ok cover
|
Issue PAID IN FULL permit | | | 7/20/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/20/2020 | | DONE |
|
|
|
This permit was created on the web by Dave Brueggemann
|