Permit Information
Permit NumberFIR14-00070
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 4024 S COUNCIL SPRING RD
Project NameThe Terraces - Bldg K
Customer NumberUDG ONLY
ePlanReviewYes
Description
The fire sprinkler scope of work consists of 6”x46± C-900 underground piping with a yard PIV.

To construct a new 11,850 square foot, one story, wood framed skilled nursing facility and related site improvements. This nursing home will contain 16 sleeping units with individual restrooms, as well as, a kitchen, dining and hearth room social area. This building will also contain a hair salon, laundry, storage and mechanical areas. This building is divided into two smoke compartments by a one-hour smoke barrier wall. This building will be fully fire sprinkled. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/27/201510/29/201510/29/2015APASS
DetailsThomas Walsh
Final inspection of FS U/G supply line. PIV and BFP valve tampers tested with fire alarm system test. All tested OK.
INSP-Sprinkler Rough-in/Hydro7/29/20157/30/20157/30/2015ACANC
DetailsThomas Walsh
Wrong permit # called in for this inspection. See permit # FIR14-00750 for inspection conducted today (7/30).
INSP-Sprinkler Rough-in7/29/20157/30/20157/30/2015ACANC
DetailsThomas Walsh
Wrong permit called in for this inspection - see permit # FIR14-00750 for inspections conducted today (7/30).
INSP-Final Inspection5/29/20156/1/20156/1/2015PCANC
DetailsThomas Walsh
Final signoff on FSUG cannot be granted until fire alarm system interface components, including tampers and waterflows, can be completed.
INSP-Sprinkler Rough-in/Hydro5/27/20155/27/20155/27/2015APASS
DetailsThomas Walsh
FSUG hydrotest from city connection to A/S BOR - 200 psi @ 2 hours - PASSED
INSP-Sprinkler Rough-in/Hydro5/26/20155/27/20155/27/2015ACANC
DetailsThomas Walsh
Hydrotest of FSUG supply lie=ne from city connection to BOR - 200 psi at 2 hours - PASSED.
INSP-Supply line flush4/21/20154/21/20154/23/2015PCANC
DetailsKatie Marron
Cancelled overbooked, rescheduled for later date.
INSP-Supply line flush4/22/20154/22/20154/22/2015PPART
DetailsKatie Marron
Supply line flush for bldg K completed satisfactory.
INSP-Supply line flush4/17/20154/17/20154/17/2015PCANC
DetailsKatie Marron
Cancelled by contractor.
Sprinkler Plan Check11/25/2014 11/25/2014 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  11/25/2014 DONE
DetailsTim Frost
CHANGE STATUS TO (ISS)  11/25/2014 DONE
DetailsCandy A. Nichols
INSP-Sprinkler Rough-in9/12/20149/15/20149/15/2014PPART
DetailsForrest France
UG fire supply line including the PIV and ductile riser okay for bury provided a plan modification is done to reflect changes in pipe route, added 45 and 90, and relocated riser room.
Sprinkler Plan Check3/7/2014 3/7/2014 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  3/7/2014 DONE
DetailsTim Frost
Permit Ready to Issue  3/7/2014 DONE
DetailsChristina Prado
Issue and Print Permit  3/7/2014 DONE
DetailsChristina Prado
Inspection Record Card- Fire3/7/2014 3/7/2014 DONE
DetailsChristina Prado
Sprinkler Plan Check2/19/2014 2/19/2014 FAIL
DetailsTim Frost
Miscellaneous action  2/19/2014 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Plan assigned to (Tim)2/19/2014 2/19/2014 DONE
DetailsTim Frost
Plan assigned to (Tim)2/12/2014 2/12/2014 DONE
DetailsTim Frost
Application received  1/28/2014 DONE
Application submitted via PDS Online on Jan 28 2014 3:34PM