INSP-Final Inspection | 8/6/2015 | 8/7/2015 | 8/7/2015 | A | PASS |
Thomas Walsh
|
|
|
Final inspection for kitchen and lobby area. Need calc placard installed. Otherwise, past final inspection.
|
INSP-Supply line flush | 8/5/2015 | 8/6/2015 | 8/6/2015 | A | PASS |
Thomas Walsh
|
|
|
Waterflow tests of the wet system risers for the first floor and second floor litchen and lobby areas. Both systems activated alarm system within 30 seconds.
|
INSP-Sprinkler Rough-in/Hydro | 5/21/2015 | 5/22/2015 | 5/22/2015 | A | PART |
Thomas Walsh
|
|
|
Hydrotest of first floor kitchen and lobby system - 200 psi @ 2 hours - PASSED NOTE: 2nd floor tested OK yesterday.
|
INSP-Sprinkler Rough-in/Hydro | 5/20/2015 | 5/21/2015 | 5/21/2015 | A | PART |
Thomas Walsh
|
|
|
Hydrotest of 2nd floor kitchen and lobby area - Passed. First floor system had leak so that one will be retested at a later date.
|
INSP-Sprinkler Rough-in/Hydro | 5/18/2015 | 5/19/2015 | 5/19/2015 | A | CANC |
Thomas Walsh
|
|
|
Found leak in the kitchen system - inspection cancelled
|
INSP-Sprinkler Rough-in/Hydro | 5/12/2015 | 5/13/2015 | 5/16/2015 | P | PASS |
Thomas Walsh
|
|
|
Kitchen rough-in inspection for levels 1 and 2
|
INSP-Sprinkler Rough-in | 1/28/2015 | 1/28/2015 | 1/28/2015 | P | PART |
Forrest France
|
|
|
Rough-in for cover finished at the 1st floor kitchen lobby area, okayed SW coverage adjacent to the fireplace. Noted cold solder issues at sprinklers each side of beam pockets.
|
INSP-Sprinkler Rough-in | 1/21/2015 | 1/22/2015 | 1/22/2015 | P | PART |
Forrest France
|
|
|
Preliminary inspection for the 3rd floor parking garage level completed. Dry pendents at the hard lid ceiling south side central okayed for cover.
|
INSP-Sprinkler Rough-in | 1/21/2015 | 1/22/2015 | 1/21/2015 | P | CANC |
Forrest France
|
|
|
This an OH/RTC inspection. Mike S is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 8/6/2014 | 8/7/2014 | 8/7/2014 | A | PART |
Forrest France
|
|
|
Overhead rough-in okay for cover at the 4th floor innovation room sheetrock ceilings and the multi-media room. Noted one damaged pendent sprinkler to be replaced.
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2014 | 8/4/2014 | 8/4/2014 | A | CANC |
Forrest France
|
|
|
Please call 45 mintures prior to inspection. Leroy is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 7/23/2014 | 7/25/2014 | 7/25/2014 | A | PART |
Scott Arellano
|
|
|
Cover approved at levels one and two only in the specific lobby areas as discussed, and restrooms .
|
Sprinkler Plan Check | 5/16/2014 | | 5/16/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/16/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 5/16/2014 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 5/16/2014 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 5/16/2014 | | 5/16/2014 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 5/16/2014 | | 5/16/2014 | | DONE |
Barbara Stitt
|
|
|
|
Sprinkler Plan Check | 5/5/2014 | | 5/5/2014 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 5/5/2014 | | FAIL |
Tim Frost
|
|
|
|
Plan assigned to (Tim) | 5/2/2014 | | 5/2/2014 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 4/29/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 29 2014 4:40PM
|