Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR14-00781
StatusFinaled
Name ALARMCO
Site Address 2800 W CHERRY LN
Project NameOak Park Bldg K Replace FACP
Customer Number 
ePlanReviewYes
Description
To replace a faulted fire alarm system with a new SK5208 in an temperature controlled NEMA enclosure. Installation of a smoke det. to protect FACP and relocation of pull stations to current mounting height code req. Re-use of existing code compliant bedroom sounders. Not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/4/20153/5/20153/5/2015APASS
DetailsForrest France
Final inspection completed, verified finishes. Fire alarm permit finaled.
INSP-Final Inspection2/5/20152/11/20152/11/2015APART
DetailsForrest France
Functional testing completed satisfactory. Items needed prior to final include; replace damaged HD at the panel enclosure, provide knox box per plan review note #9, remove "local alarm only" signage at the manual pull stations.
INSP-Final Inspection1/22/20151/27/20151/27/2015AFAIL
DetailsForrest France
Manual pull stations need relocated as indicated per the project scope and plan review comment #19, provide knox box per review note #9.
INSP-Final Inspection1/19/20151/22/20151/22/2015ADEFR
DetailsForrest France
Final Inspection for Panel Change Out and Phone Line Monitoring Phone #: ###-#### Inspection requested via web by Jeremy Berg
Alarm Plan Check11/26/2014 11/26/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/26/2014 DONE
Resubmittal approved with review comments. Projectdox updated.
Permit Ready to Issue  11/26/2014 DONE
Issue and Print Permit  11/26/2014 DONE
Inspection Record Card- Fire11/26/2014 11/26/2014 DONE
DetailsKristal Soland
Plan resubmittals received  11/25/2014 DONE
Plan assigned to (Lee)10/20/2014 10/20/2014 DONE
DetailsLee G Meredith
1st review completed  10/20/2014 FAIL
See review comments.
Miscellaneous action  10/20/2014 DONE
Emailed review comments to Jason Heath .
Application received  10/17/2014 DONE
Application submitted via PDS Online on Oct 17 2014 4:32PM