FIR-Aging Inspection | 3/3/2020 | 3/3/2020 | 3/11/2020 | | CANC |
Jim Page
|
|
|
|
Plan assigned to (Tim) | 6/12/2015 | | 6/12/2015 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/12/2015 | | 6/12/2015 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/12/2015 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 6/12/2015 | | DONE |
|
|
|
all requirments met- no additional fees
|
CHANGE STATUS TO (ISS) | | | 6/12/2015 | | DONE |
|
|
|
NO additional fees due
|
INSP-Final Inspection | 6/9/2015 | 6/10/2015 | 6/10/2015 | A | PASS |
Jim Page
|
|
|
Fire sprinkler final inspection complete
|
INSP-Sprinkler Rough-in/Hydro | 6/9/2015 | 6/9/2015 | 6/9/2015 | P | PASS |
Jim Page
|
|
|
Underground hydrostatic test passed/complete
|
INSP-Supply line flush | 6/8/2015 | 6/9/2015 | 6/9/2015 | A | PASS |
Jim Page
|
|
|
Underground flush passed/complete
|
INSP-Sprinkler Rough-in/Hydro | 6/6/2015 | 6/8/2015 | 6/8/2015 | A | CANC |
Jim Page
|
|
|
Per conversation with jobsite point of contact, Matt with Shilo, phone # ###-####, underground hydrostatic test cancelled, underground service not turned on. Shilo fire will reshedule hydrostatic test for future date.
|
INSP-Supply line flush | 6/6/2015 | 6/8/2015 | 6/8/2015 | A | CANC |
Jim Page
|
|
|
Per conversation with jobsite point of contact, Matt with Shilo, phone # ###-####, service has not been turned on, need service on to do flush, flush for the scheduled date of 8JUNE2015 cancelled, main line flush will be resheduled by Shilo Fire for a later date.
|
INSP-Supply line flush | 6/4/2015 | 6/5/2015 | 6/4/2015 | P | CANC |
Jim Page
|
|
|
This is an underground flush request. Matt is the contact. Thanks. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 6/4/2015 | 6/4/2015 | 6/4/2015 | P | PASS |
Jim Page
|
|
|
Underground 6in. fire sprinkler main approved for cover
|
INSP-Sprinkler Rough-in | 5/22/2015 | 5/26/2015 | 5/26/2015 | A | PART |
Troy Cobbley
|
|
|
Previous corrections for the basement and second floor have been addressed except for the sidewall head in the stairs to the second floor is still overspaced. Still missing water supply and contractor needs to provide non-combustible blocking to the basement fireing range. Also still need plan modifications approved for the piping re-route and additional fittings.
|
INSP-Sprinkler Rough-in/Hydro | 5/22/2015 | 5/22/2015 | 5/22/2015 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic test of the new wet systems basement, first and second floors completed satisfactory.
|
INSP-Sprinkler Rough-in | 5/20/2015 | 5/21/2015 | 5/22/2015 | P | PEND |
Forrest France
|
|
|
Regarding previous correction items
|
INSP-Sprinkler Rough-in/Hydro | 5/19/2015 | 5/20/2015 | 5/20/2015 | P | FAIL |
Troy Cobbley
|
|
|
Inspection today was for the basement and second floor rough-in and hydro tests. Hydro tests failed due to test pump and the need to modify the system. See the city approved plans for location and corrections needed which include overspaced heads, missing branchline restraints, missing flexible cplgs and missing coverage. Ball drip is installed in wrong side of check valve. Plans need to be resubmitted showing the pipin routing changes including riser nipples, additional piping heads and elevation changes.
|
INSP-Sprinkler Rough-in | 5/18/2015 | 5/19/2015 | 5/19/2015 | P | CANC |
Troy Cobbley
|
|
|
Overbooked. Rescheduled for tomorrow morning
|
INSP-Sprinkler Rough-in | 4/23/2015 | 4/24/2015 | 4/24/2015 | A | PART |
Katie Marron
|
|
|
Ok to cover main and branch and arm overs on 1st floor. A few missing hangars, contractor to correct. Verified all uprights on 1st floor, except one located above back stair well and one under front stairwell, to be verified later. All pendant locations including dry pendant drops to be verifed later. Gave OK to change from pendant to sidewall in front stair well, to be installed centered on soffit and 4" below.
|
Sprinkler Plan Check | 3/4/2015 | | 3/4/2015 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/4/2015 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 3/4/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/4/2015 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 3/4/2015 | | 3/4/2015 | | DONE |
Candy A. Nichols
|
|
|
|
Sprinkler Plan Check | 2/9/2015 | | 2/9/2015 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 2/9/2015 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Intake Approval | | | 1/23/2015 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 1/23/2015 | | 1/23/2015 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 1/23/2015 | | 1/23/2015 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 1/23/2015 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 1/23/2015 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 1/5/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 5 2015 2:46PM
|
FIR-Aging Inspection | 8/6/2020 | 8/6/2020 | | | |
Jim Page
|
|
|
|