Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR19-00522
StatusIssued
Name ABSOLUTE FIRE PROTECTION
Site Address 3100 N LAKEHARBOR LN
Project Name3050-3100 LakeHarbor
Customer Number 
ePlanReviewYes
Description
Replacement of fire alarm system. Will bring both buildings up to code.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/24/20207/29/20207/28/2020ACANC
DetailsJim Page
Please call Mike 1 hr before arriving. Phone #: ###-#### >> Inspection requested via web by James Williams Inspection cancelled from web by: James Williams
INSP-Final Inspection7/24/20207/28/20207/28/2020AFAIL
DetailsJim Page
Smoke detectors located farther than 60 inches away from doors with mag holders, smoke detectors must comply with 17.7.5.6 of NFPA72. 2 areas have audio visual notification exceeding 15 feet from end of corridor. Notatyed tenat space where a 30cd should have been provided but device was set at 15. Inspection was stopped due too defeciencies.

Please call Mike 1 hr before arriving. Phone #: ###-#### Inspection requested via web by James Williams
INSP-Final Inspection7/20/20207/24/20207/24/2020ACANC
DetailsJim Page
Cancelled per conversation with point of contact, request will be rescheduled for a later date.

Please Give Mike a call 1 hour prior to arrival. Phone #: ###-#### Inspection requested via web by James Williams
INSP-Final Inspection7/20/20207/23/20207/23/2020ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact, demo work done by others in suite 186 without permits, due too demo work troubles are on the panel. Instructed GC with RRC for space 186 the proper requirements prior to demo work.

Please Give Mike a call 1 hour prior to arrival. Phone #: ###-#### Inspection requested via web by James Williams
INSP-Final Inspection3/17/20203/20/20203/20/2020AFAIL
DetailsJim Page
Numerous walls have been added in one of the tenant spaces, TI is marked on city approved drawings. Wall layout affects audio visual coverage, floor plan must match approved drawings, inspection was stopped.

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Alarm Testing10/29/201910/31/201910/31/2019APART
DetailsJim Page
Fire alarm inspection/testing for suite 180 is complete.

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Alarm Testing10/28/201910/29/201910/28/2019ACANC
DetailsJim Page
Needs to be done at 7:00am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Alarm Testing10/25/201910/28/201910/28/2019AFAIL
DetailsJim Page
Sounder base and A/V devices do not sync during operation. Pull station in 180 tenant space did not operate when activated.

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Alarm Testing10/23/201910/25/201910/25/2019AFAIL
DetailsJim Page
Relocate 2 smoke detectors that are overspaced. Relocate smoke detector that is to close to HVAC register or relocate HVAC register to get minimum of 36 inches away. Sync sounder base to A/V devices in space, sound did not sync.

Needs done at 7:00 am Phone #: ###-#### Inspection requested via web by Sam Ball
Plan assigned to (Lee)8/12/2019 8/13/2019 DONE
DetailsLee G Meredith
1st review completed  8/13/2019 PASS
Alarm Plan Check8/13/2019 8/13/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/13/2019 DONE
Plan mod passed. No additional comments.
Permit Ready to Issue  8/13/2019 DONE
CHANGE STATUS TO (ISS)  8/13/2019 DONE
Plan Modification Accepted  8/12/2019 DONE
addressing per mary with absolute fire protection
Plan resubmittals received  7/18/2019 DONE
Alarm Plan Check7/18/2019 7/18/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/18/2019 DONE
Passed with review comments.
Permit Ready to Issue  7/18/2019 DONE
met
Issue and Print Permit  7/18/2019 DONE
Application received  7/15/2019 DONE
Application submitted via PDS Online on Jul 15 2019 6:30AM
Plan assigned to (Lee)7/15/2019 7/15/2019 DONE
DetailsLee G Meredith
1st review completed  7/15/2019 FAIL
Several areas have inadequate visible notification coverage. 2nd story exit appears to lead directly outside without a stair or landing. Scale graph is incorrect. Returned to Mary for corrections and additional information.