INSP-Final Inspection | 4/27/2020 | 4/28/2020 | 4/28/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Previous items corrected. Buck Phone #: ###-####
|
Issue and Print Permit | | | 4/24/2020 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/23/2020 | | DONE |
|
|
|
Rita requested the workflow to be opened for as builts.
|
Plan assigned to (Lee) | 4/23/2020 | | 4/23/2020 | | DONE |
Lee G Meredith
|
|
|
as built
|
Intake Approval | | | 4/23/2020 | | PASS |
|
|
|
|
1st review completed | | | 4/23/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 4/23/2020 | | 4/23/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/23/2020 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 4/23/2020 | | DONE |
|
|
|
**DO NO REISSUE - AS BUILT**
|
INSP-Final Inspection | 4/22/2020 | 4/22/2020 | 4/22/2020 | P | CANC |
Jim Page
|
|
|
Phone #: ###-#### >> Inspection requested via web by Ken Webster Inspection cancelled from web by: Ken Webster
|
INSP-Final Inspection | 4/10/2020 | 4/13/2020 | 4/13/2020 | A | FAIL |
Jim Page
|
|
|
Provide mag lock release during general fire alarm for de-escalation room. Approved drawings will need to reflect the addition of the speaker/strobe added by kitchen hood instead of just speaker, a strobe needed to be added for proper visual coverage. CO2 detectors need to activate audio visual notification per alarm matrix. All other initiating devices have been tested without issues, hood reports to fire panel as required.
Buck - Screened for COVID 19 symptosm Phone #: ###-####
|
Plan resubmittals received | | | 9/27/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 9/27/2019 | | 9/27/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/27/2019 | | DONE |
|
|
|
Passed with review commets.
|
Permit Ready to Issue | | | 9/27/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 9/27/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 8/27/2019 | | 8/27/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 8/27/2019 | | FAIL |
|
|
|
Detector spacing incorrect, needs a smoke detector at the fire alarm panel, need ceiling height for gym and cafeteria.
|
Application received | | | 8/26/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 26 2019 3:18PM
|