Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR19-00853
StatusFinaled
Name TKG PROTECTION SYSTEMS
Site Address 2909 W ELDER ST
Project NameBoise Airport Hotel
Customer Number 
ePlanReviewYes
Description
Simple Suites - Complete New Fire Alarm System in a new 4 story hotel with elevator controls. This work is associated with BLD18-03245.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/23/20203/26/20203/26/2020APASS
DetailsTroy Cobbley
Permit finaled. Phone #: ###-#### Inspection requested via web by John Lopez
INSP-Final Inspection3/19/20203/20/20203/20/2020ACANC
DetailsTroy Cobbley
Canceled per John.. Phone #: ###-#### Inspection requested via web by John Lopez
INSP-Alarm Testing3/19/20203/19/20203/19/2020PDONE
DetailsTroy Cobbley
To final project I need the plan mods, verify changes in the field, shunt in elevator repaired, map and final doc's

Troy Phone #: ###-####
Permit Ready to Issue  3/19/2020 DONE
**plan mod - do not reissue**
CHANGE STATUS TO (ISS)  3/19/2020 DONE
INSP-Final Inspection3/17/20203/18/20203/18/2020PFAIL
DetailsTroy Cobbley
Testing today consisted of a walk through for business. See city approved plans for minor modifications needed for notification devices. Plan resubmittals are needed to show the changes. We also tested the smoke detectors and notification on the 4th floor. Need to test 3rd, 2nd, 1st floors and elevator.

Phone #: ###-#### Inspection requested via web by John Lopez
Plan resubmittals received  3/18/2020 DONE
John requested the work flow to be opened for an as built #2
Plan assigned to (Lee)3/18/2020 3/18/2020 DONE
DetailsLee G Meredith
as built 2
1st review completed  3/18/2020 DONE
Alarm Plan Check3/18/2020 3/18/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/18/2020 DONE
Minimum $65 review fee for plan mod.
INSP-Alarm Testing3/13/20203/13/20203/13/2020PDONE
DetailsTroy Cobbley
Lee verified the head end equipment and the interconnection with the fire sprinkler devices. He noted that there may be sync issues. Candellas and smoke detectors need tested as well as elevator recall.

John Phone #: ###-####
CHANGE STATUS TO (ISS)  3/13/2020 DONE
plan mod
INSP-Alarm Testing3/10/20203/11/20203/11/2020PNR
DetailsTroy Cobbley
Plan mods are needed showing the correct fire alarm panel model installed and the correct means of communication installed. These items currently do not match the approved plans. No testing performed.

Phone #: ###-#### Inspection requested via web by John Lopez
Plan resubmittals received  3/11/2020 DONE
as built requested by John Lopez from TKG Protection
Plan assigned to (Lee)3/11/2020 3/11/2020 DONE
DetailsLee G Meredith
as built- part changes and path of comunication changes
1st review completed  3/11/2020 DONE
Alarm Plan Check3/11/2020 3/11/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/11/2020 DONE
As Built - No fee
Permit Ready to Issue  3/11/2020 DONE
plan mod
Issue and Print Permit  2/12/2020 DONE
Plan assigned to (Lee)2/4/2020 2/6/2020 DONE
DetailsLee G Meredith
plan mod
1st review completed  2/6/2020 DONE
Alarm Plan Check2/6/2020 2/6/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/6/2020 DONE
Plan mod passed. No additional review comments provided. Minimum review fee of $65 is due.
Permit Ready to Issue  2/6/2020 DONE
plan mod approved
Plan Modification Accepted  2/4/2020 DONE
John requested the Eplan workflow to be reopend over the phone for changes in the system
Plan resubmittals received  12/11/2019 DONE
1st review completed  12/11/2019 DONE
Alarm Plan Check12/11/2019 12/11/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/11/2019 DONE
Passed with review comments.
Permit Ready to Issue  12/11/2019 DONE
MET
Issue and Print Permit  12/11/2019 DONE
Plan assigned to (Lee)11/14/2019 11/14/2019 DONE
DetailsLee G Meredith
Intake Approval  11/14/2019 FAIL
Smoke fire damper detection missing, needs engineer of record review, detectors may be too close to fixed cooktops. Returned to John Lopez and sent him an email listing issues.
Application received  11/13/2019 DONE
Application submitted via PDS Online on Nov 13 2019 5:38PM