INSP-Final Inspection | 3/31/2020 | 3/31/2020 | 3/31/2020 | P | PASS |
Jim Page
|
|
|
Previously noted item has been corrected, final inspection for scope of work is complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/24/2020 | 3/25/2020 | 3/25/2020 | P | FAIL |
Jim Page
|
|
|
In-duct detector is mounted on the exterior of the ductwork outside exposed to the elements, detector is outside of its listed environment, provide conditioning for duct detector.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Plan assigned to (Lee) | 3/24/2020 | | 3/24/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 3/24/2020 | | PASS |
|
|
|
|
1st review completed | | | 3/24/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 3/24/2020 | | 3/24/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/24/2020 | | DONE |
|
|
|
Quick permit passed with drawing notes / requirements.
|
Permit Ready to Issue | | | 3/24/2020 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 3/24/2020 | | DONE |
|
|
|
|
Application received | | | 3/23/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 23 2020 1:20PM
|