INSP-Conference | 7/16/2020 | 7/16/2020 | 7/16/2020 | P | DONE |
Jim Page
|
|
|
Fire conference is complete. Advised Dustin with MCALVAIN too email Joe Bruce, Fire Section Supervisor too see if a variance can be granted to have the PIV closer than 40 feet to the building. PIV location was compromised due too fire truck access, PIV is no longer in the parking lot island as designed, island had to be shortened for fire truck access. A re-submittal will be required for underground supply re-route as noted on previous inspection and too show new location for PIV.
|
INSP-Sprinkler Rough-in | 7/16/2020 | 7/16/2020 | 7/16/2020 | P | CANC |
Jim Page
|
|
|
Request was for a conference, this request is cancelled.
Screened- Dustin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 7/7/2020 | 7/8/2020 | 7/8/2020 | A | PART |
Troy Cobbley
|
|
|
The 6" supply line is ok to cover except where the PIV needs to be installed and the connection to the IBR. The remote FDC piping can be covered from the building to the end of the first 21' of pipe.
Underground -Dustin *screened* Phone #: ###-####
|
INSP-Supply line flush | 7/2/2020 | 7/2/2020 | 7/2/2020 | A | DONE |
Jim Page
|
|
|
Re-route supply main flush witnessed via video.
|
INSP-Sprinkler Rough-in | 7/1/2020 | 7/2/2020 | 7/2/2020 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for fire service main underground re-route complete, plans need to reflect re-route before final inspection, re-route approved for cover at contractors descretion provided re-route does not effect water calculations for down-stream fire sprinkler services.
Dustin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 6/30/2020 | 7/1/2020 | 7/1/2020 | P | FAIL |
Troy Cobbley
|
|
|
Need drawings and small documents, need piping uncovered for inspection, Shilo needs to be involved in installation as per state code, need flushing of the modified/new piping.
underground- Dustin *screened* Phone #: ###-####
|
INSP-Sprinkler Rough-in | 6/4/2020 | 6/4/2020 | 6/4/2020 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for IBR and FDC building stub in compete, areas inspected approved for cover. Remaining underground to be inspected at a later date.
|
Issue and Print Permit | | | 5/29/2020 | | DONE |
|
|
|
|
Application received | | | 5/14/2020 | | DONE |
|
|
|
Application submitted via PDS Online on May 14 2020 2:17PM
|
Intake Approval | | | 5/14/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 5/14/2020 | | 5/14/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 5/14/2020 | | 5/14/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
1st review completed | | | 5/14/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/14/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 5/14/2020 | | DONE |
|
|
|
|