INSP-Final Inspection | 8/3/2020 | 8/4/2020 | 8/4/2020 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please. He''s requesting a NOON inspection time ff possible please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 | P | CANC |
Troy Cobbley
|
|
|
Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please he is requesting a NOON inspection time if at all possible please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in | 7/31/2020 | 8/3/2020 | 8/3/2020 | A | PASS |
Jim Page
|
|
|
Previously noted items have been coprrected, cover is approved.
Contact Andrew Larson ###-#### he is requesting a 8:30 AM RTC Insp if at all possible, if this can not happen please call him.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
Plan assigned to (Stumbaugh) | 7/30/2020 | | 7/31/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 7/31/2020 | | 7/31/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/31/2020 | | DONE |
Mark Stumbaugh
|
|
|
Review Time 1hr
No new devices
|
Permit Ready to Issue | | | 7/31/2020 | | DONE |
|
|
|
PLAN MOD
|
CHANGE STATUS TO (ISS) | | | 7/31/2020 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 7/29/2020 | 7/30/2020 | 7/30/2020 | P | FAIL |
Jim Page
|
|
|
2 90's have been added on the 2 inch piping supplying branchlines in the rooms (2 per line, a total of 10 nhave been added), 90's need to be shown on plans and calcs checked to make sure 90's can remain in place. Provide hangers in areas where hangers on branch lines are overspaced. Provided branch line restraints as shown on city approved drawings cover for area of work is not approved..
Contact Andrew Larson ###-#### 30 min prior to RTC Insp start please. Andrew is requesting a 12PM inspection time if at all possible.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
Plan Modification Accepted | | | 7/30/2020 | | DONE |
|
|
|
Terri from Phoenix called to request a plan mod
|
Plan resubmittals received | | | 6/26/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 6/26/2020 | | 6/26/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/26/2020 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 6/26/2020 | | DONE |
|
|
|
MET
|
Issue and Print Permit | | | 6/26/2020 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/24/2020 | | 6/25/2020 | | FAIL |
Mark Stumbaugh
|
|
|
|
1st review completed | | | 6/25/2020 | | FAIL |
Mark Stumbaugh
|
|
|
|
Application received | | | 6/24/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 24 2020 1:54PM
|
Intake Approval | | | 6/24/2020 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 6/24/2020 | | 6/24/2020 | | DONE |
Mark Stumbaugh
|
|
|
|