Final | 6/24/2020 | 6/25/2020 | 6/25/2020 | P | PASS |
Brian Scoles
|
|
|
Contact Kurtis for access ###-#### Phone #: ###-#### Inspection requested via web by John Bertram- final ok
|
Final | 5/22/2020 | 5/26/2020 | 5/26/2020 | P | FAIL |
Chad Schwendiman
|
|
|
Contact Kurtis to make sure of garage access ###-#### Phone #: ###-#### Inspection requested via web by John Bertram - need to install a insulation shield on B-vent
|
Mec-Aging Inspection | 4/9/2020 | 4/9/2020 | 4/9/2020 | | FAIL |
Brian Scoles
|
|
|
needs final inspection called in when ready- BLD still open
|
Pressure Test | 9/23/2019 | 9/24/2019 | 9/24/2019 | P | CANC |
Brian Scoles
|
|
|
Call Kurtis ###-#### to meet you, 15 to 20 minute heads up if possible, house is vacant, gas pressure test on back patio at meter, fan vents have been roughed in Phone #: ###-#### Inspection requested via web by John Bertram- 20lb gas pass whole system
|
Rough-in | 9/24/2019 | 9/24/2019 | 9/24/2019 | P | PASS |
Brian Scoles
|
|
|
Call Kurtis ###-#### to meet you, 15 to 20 minute heads up if possible, house is vacant, gas pressure test on back patio at meter, fan vents have been roughed in Phone #: ###-#### Inspection requested via web by John Bertram- R/I ok- need to insulate all bare metal in garage, attic and crawl space on new ducting by final- dryer vent wall needs firred out- need insulation shield on water heater/furnace b vent with 1" clearance in attic- condensate drain needs to be 3/4" pvc to outside
|
Issue PAID IN FULL permit | | | 9/17/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/17/2019 | | DONE |
|
|
|
This permit was created on the web by John Bertram
|