Final | 6/25/2020 | 6/25/2020 | 6/25/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson- final ok
|
Final | 6/24/2020 | 6/25/2020 | 6/25/2020 | A | FAIL |
Brian Scoles
|
|
|
GARAGE CODE: 7060 Phone #: ###-#### Inspection requested via web by Kristy Watson- 1- need approved man j onsite 2- a/c needs locking caps on service ports 3- lineset needs to be off ground 3 and a half inches covered by landscaping rocks
|
Mec-Aging Inspection | 5/27/2020 | 5/27/2020 | 5/27/2020 | | FAIL |
Brian Scoles
|
|
|
needs called in for when ready
|
Rough-in | 10/31/2019 | 11/1/2019 | 11/1/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson- R/I ok- need to support crawl supply duct off ground at crawl entrance by final and seal dryer duct to termination box by final - talked to Kristy about this
|
Pressure Test | 11/1/2019 | 11/1/2019 | 11/1/2019 | A | PASS |
Brian Scoles
|
|
|
20lb gas pass tagged meter location
|
Rough-in | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson 1- gas gauge does not zero out- replace 2- need to seal all spotwelds on all R/A and supply boots 3- man j shows 2 supply runs in bedrooms 2&3 only has one installed- need to add per man j or resubmit to city for approval as installed 4- exposed insulation on flex duct in crawl needs vapor barrier installed 5- main supply trunk in crawl pinched off due to plumbing drain at crawl entrance
left notice front window
|
Pressure Test | 10/31/2019 | 10/31/2019 | 10/31/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson- gauge doesnt zero out- replace
|
Issue PAID IN FULL permit | | | 10/28/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/28/2019 | | DONE |
|
|
|
This permit was created on the web by Kristy Watson
|