Staff review | 8/11/2020 | 8/11/2020 | 8/11/2020 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 8/11/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 8/11/2020 | | 8/11/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/11/2020 | | DONE |
|
|
|
As built - no fee.
|
Permit Ready to Issue | | | 8/11/2020 | | DONE |
|
|
|
as built approved
|
CHANGE STATUS TO (ISS) | | | 8/11/2020 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 8/4/2020 | | 8/11/2020 | | DONE |
Lee G Meredith
|
|
|
asbuitl request per Mary -adding power supply
|
Plan resubmittals received | | | 8/4/2020 | | DONE |
|
|
|
asbuilt per Mary
|
INSP-Final | 7/29/2020 | 8/3/2020 | 8/3/2020 | A | FAIL |
Troy Cobbley
|
|
|
Provide 18AH batteries, resubmit plans showing zone expander/power supply, clean up wiring, meet NEC for the interconnection between the FACP and the Zone Expander panel (exposed wire may need to be in conduit?). Please call 20-30 minutes prior to inspection. You will be meeting technician Jason Petty on site. Phone #: ###-#### Inspection requested via web by jason petty
|
Staff review | 6/24/2020 | 6/24/2020 | 6/25/2020 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/25/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 6/25/2020 | | 6/25/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/25/2020 | | DONE |
|
|
|
Passed with review comments.
|
Permit Ready to Issue | | | 6/25/2020 | | DONE |
|
|
|
|
Issue and Courier | | | 6/25/2020 | | DONE |
|
|
|
Emailed Shelley to inform her this permit has been issued.
|
Plan assigned to (Lee) | 6/24/2020 | | 6/25/2020 | | DONE |
Lee G Meredith
|
|
|
|
Application received | | | 6/24/2020 | | |
|
|
|
|
Miscellaneous action | | | 6/24/2020 | | DONE |
|
|
|
Emailed Shelley NAF number
|
INSP-Final | 8/13/2020 | 8/20/2020 | | P | |
Troy Cobbley
|
|
|
Please call 20-30 minutes prior to inspection. You will be meeting technician Jason Petty on site. Phone #: ###-#### >> Inspection requested via web by jason petty
|