Permit Information
Permit NumberBLD19-00323
StatusIssued
Name KW HOMES INC
Site Address 3027 N COLE RD
Project NamePeking Tokyo Asian Bistro
Customer NumberBLD19-00541 DEMO
ePlanReviewYes
Description
(PEKING TOKYO ASIAN BISTRO) **2nd PLAN MODIFICATION 05-11-20 for modifications to the mechaincal design and sheet M1.0** **PLAN MODIFICATION 9-30-19 To modify truss reinforcing for fire sprinkler pipe between trusses, SEE SHEET S-1.00.** This building is adding a fire sprinkler system for building area increase and for fire area. Building to the east (Sockeye Brewing) shall also be retrofitted with fire sprinklers through an Upgrade Agreement (attached to this case) at a later date. Permit to remodel an existing 2,687 square foot mercantile space into a restaurant. Work is to include new non-bearing interior walls, two toilet rooms to be accessible to the disabled, dining area, sushi bar, plumbing, electrical, and mechanical work; and interior finishes in compliance with Ch. 8 of the 2015 IBC. A new kitchen with a new Type I Hood, new UL listed kitchen equipment, and a portion of the concrete slab will be saw cut and removed to facilitate underslab plumbing and a new concrete slab on grade will be placed to patch the concrete after the plumbing is complete. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any installation work on such systems. **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection6/26/20206/26/20206/30/2020 PEND
DetailsTell Riley
BLD-Conference4/8/20204/8/20204/8/2020PDONE
DetailsTell Riley
conference with contractor, mechanical contractor and inspectors, was scheduled under wrong permit//will need to have calcs and engineers approval and or fix for RTU units that have changed location and size, drawings including mechanical will need to be submitted for plan modification//
BLD-Framing/Rough-in2/12/20202/13/20202/13/2020APART
DetailsTell Riley
call ahead // Kent Phone #: ###-####//insulation installed in existing walls that were open //backing added for accesibility requirements//ok to cover vertical wall ONLY//still need mechanical and fire sprinkler sign offs prior to covering any ceilings//no access to fire riser room--also will need inspected for rated walls and penetrations//
BLD-Framing/Rough-in2/3/20202/4/20202/4/2020PFAIL
DetailsTell Riley
call ahead // Ken Phone #: ###-####//need fire sprinkler roug in completed//add backing for Accessibility//secure demising wall studs//provide wall assembly for 1 hr room at fire riser//
BLD-Framing/Rough-in1/17/20201/17/20201/17/2020PPART
DetailsTell Riley
Ken- please call for access Phone #: ###-####//issues with addresses and permits for this building//told Ken he needs to go downtown and fix address issues//need mechanical permit//ok to insulate exterior walls and one side demising wall//
BLD-Framing/Rough-in12/26/201912/26/201912/26/2019PCANC
DetailsTell Riley
metal stem wall // Kent Phone #: ###-####/ Ken had questions on demising wall--plans show to underside of roof sheathing--wall stops at roof insulation--refered him to architect//some walls have been one sided--asked him to leave uncovered until all trades passed and framing is approved//
BLD-Framing/Rough-in11/21/201911/21/201911/21/2019PPART
DetailsTell Riley
Call ahead 30 minutes - truss bracing // Kent Phone #: ###-####truss bracing // Kent Phone #: ###-####//engineering and engineers letter from site visit and approval onsite dated Nov 20, 2019 stamped and signed reviewed onsite//trusses ok per engineer//
BLD-Wall Bracing11/19/201911/19/201911/19/2019PCANC
DetailsTell Riley
call for keycode access // Kim Phone #: ###-####//CN posted still needs completed//updated engineering needed to reflect what was performed onsite that does not reflect the approved truss fixes//no wall bracing inspection needed at this time//
BLD-Framing/Rough-in11/6/201911/7/201911/7/2019AFAIL
DetailsTell Riley
ken Phone #: ###-####//CN posted//truss fixes do not all reflect engineered fixes//see CN onsite//