Permit Information
Permit NumberBLD20-00337
StatusIssued
Name BENITON CONSTRUCTION
Site Address 3555 N MILWAUKEE ST
Project NameValley View Elementary School
Customer Number 
ePlanReviewYes
Description
(Project Management- Ron Hill) EXPEDITED REVIEW Construct a new 54,700 SF., 2 story elementary school with 38,600 sq. ft. first story and a 16,100 sq. ft. second story. This school will replace the existing elementary school on this site. Mechanical commissioning report required to be submitted to Mechanical inspector supervisor for final inspection. This building is fully fire sprinklered and alarmed as an educational occupancy over 12,000 sq. ft. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Concrete8/10/20208/10/20208/10/2020PPART
DetailsTell Riley
Slab on grade- Chase *screened* Phone #: ###-####//ok pend specials//
BLD-Other8/6/20208/7/20208/7/2020APART
DetailsTell Riley
screened - masonry // Chase Phone #: ###-####//masonry for gym walls//pend special inspections//
BLD-Foundation8/4/20208/4/20208/4/2020PDEFR
DetailsTell Riley
*Screened* masonary & foundation - Chase Phone #: ###-####//defer to special inspections//
BLD-Concrete7/30/20207/30/20207/30/2020PPART
DetailsTell Riley
Screened- slab on grade inspection- Chase Phone #: ###-####//ok pending specials//
BLD-Other7/30/20207/30/20207/30/2020PPART
DetailsTell Riley
Screened- massonary-reba inspection- Chase Phone #: ###-####//ok pending specials//
BLD-Footing7/28/20207/29/20207/29/2020APART
DetailsTell Riley
Chase *screened* Phone #: ###-####//last of the interior footers and piers--3 exterior footers//ok pending specials//
BLD-Concrete7/23/20207/23/20207/23/2020PPART
DetailsTell Riley
Chase *screened* Phone #: ###-####//last of area A slab, ok pending special inspections//east part of area B slab, vapor barrier ok, no wire mesh installed yet--pend specials//
BLD-Footing7/20/20207/21/20207/21/2020APART
DetailsTell Riley
Chase Phone #: ###-####//interior footing pads in area b and c//mat footings--need to add full length verts at correct size where short verts were installed--will have checked by special inspector// all others appear ok//pending specials//
BLD-Concrete7/14/20207/14/20207/14/2020PPART
DetailsTony Young
Chase *screened* Phone #: ###-####// pending special inspection
BLD-Foundation7/8/20207/9/20207/9/2020APART
DetailsTell Riley
screened // Chase Phone #: ###-####//areas b and c exterior foundation//ok pending specials//interior foundation piers and elevator pit as well//
BLD-Footing7/1/20207/2/20207/2/2020APART
DetailsMike Jordan
Screened // Chase Phone #: ###-####. Interior column pads and exterior footing in areas b and c. Ok to place pending special inspection.
BLD-Foundation6/25/20206/26/20206/26/2020APART
DetailsTell Riley
screened // Chase Phone #: ###-####//part of Area C foundation walls//ok pend specials//maintain bar clearances//
BLD-Footing6/22/20206/23/20206/23/2020APART
DetailsTell Riley
Chase *screened* Phone #: ###-####//part of area C footings//ok per plans pending all specials//
BLD-Footing6/17/20206/17/20206/17/2020PPART
DetailsTell Riley
Chase Phone #: ###-####//add top mat bar in F7A footings//areas ok signed off on plans//interior footing column pads//pend all specials//
BLD-Foundation6/12/20206/12/20206/12/2020PPART
DetailsTell Riley
Chase Phone #: ###-####//GYM slab//bar per plan//VB installed and taped//pend all specials//
BLD-Foundation6/10/20206/11/20206/11/2020APART
DetailsTell Riley
Chase *screened* Phone #: ###-####//portions of area B and C walls//ok when bar clearances are corrected//pend all specials//
BLD-Footing6/10/20206/11/20206/11/2020ACANC
DetailsTell Riley
Chase *screened* Phone #: ###-####//previously inspected area A footing//
BLD-Foundation6/8/20206/9/20206/9/2020APART
DetailsTell Riley
Screened-Chase Phone #: ###-####-7515//area A walls will be complete with this pour//ok pending all specials//
BLD-Footing6/4/20206/5/20206/5/2020APART
DetailsTell Riley
screened // Chase Phone #: ###-####//area B footings-partial//ok eonding all special inspection approvals//
BLD-Foundation6/2/20206/3/20206/3/2020APART
DetailsTell Riley
screened - Chase Phone #: ###-####//continued foundation area A//appears ok//pend all specials//
BLD-Footing6/2/20206/3/20206/3/2020APART
DetailsTell Riley
screened - Chase Phone #: ###-####//contiued footings area A//appears to be ok//pend specials//
BLD-Foundation5/28/20205/29/20205/29/2020APART
DetailsTell Riley
screened // Chase Phone #: ###-####//footing pads and large mat footing in area A//marked on plans, ok pending specials//
BLD-Footing5/26/20205/27/20205/27/2020APART
DetailsTell Riley
asked for between 9-11 if possible // Jason Phone #: ###-####//more area A footings for gym//footing sizes ok per plans//pending all special inspections//
BLD-Footing5/21/20205/21/20205/21/2020PDEFR
DetailsTell Riley
screened // Chase Phone #: ###-####//defer to specials//
BLD-Foundation5/19/20205/19/20205/19/2020PPART
DetailsTell Riley
CHACE Phone #: ###-####//Area A exterior foundation wall 2" foam insulation installed//
BLD-Foundation5/14/20205/15/20205/15/2020APART
DetailsTell Riley
asking before 9am // Chase Phone #: ###-####//need to maintain clearances on bar, special inspector will be onsite and confirm//areas with electrical conduit will need permit and inspection prior to cover//special inspector onsite, pending his approvals//Area A walls and partial footing//
BLD-Footing5/7/20205/8/20205/8/2020APART
DetailsMike Jordan
*screened* Chase, requests between 10 & noon Phone #: ###-####. Area A Footings, work in progress. Work that ws completed was ok. Ok to place concrete pending special inspection.