Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberELE19-01688
StatusIssued
Name QUALITY ELECTRIC INC
Site Address 111 W STATE ST
Project Name 
Customer Number19005
ePlanReviewNo
Description
New: Furnish and install complete electrical package per approved plans for St Lukes Central Plant. Includes power, lighting, emergency power system, lightning protection, fire alarm, data and security systems.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service8/5/20208/6/20208/6/2020APASS
DetailsJames Ady
Screened- Jamon Phone #: ###-#### All documentation received. Breaker testing complete, afci rating ok. p/s u/g n ok
Electrical Rough-In8/3/20208/4/20208/4/2020APART
DetailsJames Ady
screened - service gear and transformers // Jamie Phone #: ###-#### Serfvice gear and transformers checked. Transformersok to cover, Waiting on Performance testing and AFCI rating.
Electrical Rough-In6/1/20206/1/20206/1/2020PPASS
DetailsJames Ady
Control room wall rough-in Jamie Phone #: ###-#### Continued duct band and Control room walls only ok to cover
Conference5/22/20205/26/20205/26/2020APASS
DetailsJames Ady
8:30 Am Consult Main hospital Phone #: ###-#### Inspection requested via web by Mark M Discussed requirments of 110.26E(1) Dedicated electrical equipment space. Water lines above equipment must be above structural ceiling to be alowed. Will build a structural soffit around lines to comply with code.
Electrical Rough-In5/22/20205/22/20205/22/2020APASS
DetailsJames Ady
CUP Small offices Sub basement Phone #: ###-#### Inspection requested via web by Mark M walls only ok to cover
Electrical Rough-In5/4/20205/4/20205/4/2020PPASS
DetailsJames Ady
Screened- duct bank inspection-Jamie Phone #: ###-#### Short section in Basement hall ok to cover
Electrical Rough-In4/23/20204/23/20204/23/2020PPASS
DetailsJames Ady
duct bank - screened // Jamey Phone #: ###-#### underground for generator feeds and control wire ok to cover
Electrical Rough-In4/21/20204/22/20204/22/2020PCANC
DetailsJames Ady
Screened- Duct Bank inspection-Jamie- Phone #: ###-####
Electrical Rough-In4/8/20204/8/20204/8/2020PPASS
DetailsJames Ady
Jamie *cleared* Phone #: ###-#### Underground between Shipping and CUP along side tunnel ok to cover. UFER ok to cover
Electrical Rough-In4/3/20204/6/20204/6/2020APASS
DetailsJames Ady
St. Luke''s - caller uncertain about cleared status - will call and willing to video // Jamie Phone #: ###-#### Remaining area on level G
Electrical Rough-In4/3/20204/3/20204/3/2020PPASS
DetailsRock A. Hudson
Other electrodes such as underground water pipe and building steel will make up a grounding electrode system. Notes due to large amount of debris in area 3/0 bare copper conductor is positioned.
Conrete encased electrode rough in ok cover.
Rough-In Permanent Service4/2/20204/3/20204/3/2020ACANC
DetailsRock A. Hudson
This is actually a Ufer ground inspection Phone #: ###-#### Inspection requested via web by Scott Campbell
Called contact and informed this building permit is suspended job site list posted 4-2-2020. Asked to photo installation and recall when ready.
Electrical Rough-In4/2/20204/3/20204/3/2020ACANC
DetailsRock A. Hudson
Rough-In Walls for G level Phone #: ###-#### Inspection requested via web by Scott Campbell Called contact and informed this building permit is on the suspended job lite list posted
4-2-2020. Asked them to take several photos and recall for Monday when the normal inspector is scheduled to be back at work.
Electrical Rough-In2/24/20202/24/20202/24/2020PPASS
DetailsJames Ady
Wall inspection for level G. Contact is Tony Holt. Phone #: ###-#### Inspection requested via web by Scott Campbell Level G walls only areas marked on contractor power print
Electrical Rough-In2/12/20202/13/20202/13/2020APASS
DetailsJames Ady
underground inspection for transformer vault Phone #: ###-#### Inspection requested via web by Scott Campbell transformer vault floor only ok to cover
Electrical Rough-In1/28/20201/29/20201/29/2020PPASS
DetailsJames Ady
Underground inspection, 1st and Jefferson tunnel. Contact is Tony Holt. Phone #: ###-#### Inspection requested via web by Scott Campbell Section 2 headed west towards N2 plant ok to cover
Electrical Rough-In1/21/20201/21/20201/21/2020PPASS
DetailsJames Ady
Underground cover inspection - contact is Tony Holt Phone #: ###-#### Inspection requested via web by Scott Campbell Underground conduit in floor of SE tunnel to main hospital ok to cover
Electrical Rough-In12/3/201912/3/201912/3/2019PPASS
DetailsJames Ady
Contact is Tony Holt. Underground rough-in inspection Phone #: ###-#### Inspection requested via web by Scott Campbell Duct bank on South side of building ok to cover
Electrical Rough-In11/20/201911/20/201911/20/2019PPASS
DetailsJames Ady
Contact is Tony Holt Phone #: ###-#### Inspection requested via web by Scott Campbell Final deck pour ok to cover
Electrical Rough-In11/6/201911/6/201911/6/2019PPASS
DetailsJames Ady
Contact is Tony Holt. Rough in inspection for first floor desk. Phone #: ###-#### Inspection requested via web by Scott Campbell First floor deck pour 1 ok to cover
Electrical Rough-In9/27/20199/30/20199/30/2019APASS
DetailsJames Ady
Cover inspection - contact is Rene Ramakers Phone #: ###-#### Inspection requested via web by Scott Campbell Sleeves and 3/4in conduits in 1st level concrete ok to cover.
Electrical Rough-In9/4/20199/4/20199/4/2019PPASS
DetailsJames Ady
COVER INSPECTION, CONTACT IS RENE RAMAKERS Phone #: ###-#### Inspection requested via web by Scott Campbell Underground moving E ok to cover
Electrical Rough-In8/15/20198/16/20198/16/2019APASS
DetailsJames Ady
Cover inspection, contact is Rene Ramakers Phone #: ###-#### Inspection requested via web by Scott Campbell SE corner Underground only ok to cover
Electrical Rough-In8/7/20198/8/20198/8/2019APASS
DetailsJames Ady
Contact is Rene Ramakers - wall cover inspection Phone #: ###-#### Inspection requested via web by Scott Campbell South concrete wall LL3 ok to cover
Conference5/8/20195/8/20195/8/2019PPASS
DetailsJames Ady
Conference request at Quality Electric office, 5272 W. Irving St - please call Rene Ramakers to set a time to do so. ###-####. Thanks Phone #: ###-#### Inspection requested via web by Scott Campbell Talked about Service entrance requirments. Must be considered "Outside the building" Can be ran under minimum of 2in concrete. Pull box below main gear ok.