Permit Information
Permit NumberELE19-03509
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 1032 S BROADWAY AVE
Project Name 
Customer Number19-033
ePlanReviewNo
Description
New: Provide the electrical work associated with the Broadway Mixed Use building.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/12/20203/13/20203/13/2020PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Corrections made final ok
Final3/4/20203/5/20203/5/2020AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jeremy Cloud 110.3 GFCI Hot grnd revers Elevator pit. GFCI dead SE Stair well door Exterior. Wall pack needs installed/repaired above main service. Pig tail needs install for sprinkler time clock. 440.24 Max overcurrent for 4 RTU's is 40A 45A installed. 330. MC Stapped Less than 1 1/4in from face of stud misc areas on exterior walls
Permanent Service1/23/20201/24/20201/24/2020APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jeremy Cloud p/s u/g n ok
Electrical Rough-In11/26/201911/27/201911/27/2019APASS
DetailsRock A. Hudson
Matt Garcia ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Riser room switch wall, south wall pack, up parapet receptacles in walls rough in ok cover
Electrical Rough-In10/3/201910/4/201910/4/2019PPASS
DetailsJames Ady
Inspect underground to backfill. Matt Garcia ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud 1in to monument sign, 3in from mech room to service and L.V sleaves to elevator shaft ok to cover
Electrical Rough-In9/30/201910/1/201910/1/2019APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground from transformer to building only ok to cover
Electrical Rough-In9/30/201910/1/20199/30/2019PCANC
DetailsJames Ady
Underground to cover Phone #: ###-#### >> Inspection requested via web by Jeremy Cloud Inspection cancelled from web by: Jeremy Cloud
Electrical Rough-In9/25/20199/25/20199/25/2019PPASS
DetailsJames Ady
Inspect Ufer Phone #: ###-#### Inspection requested via web by Jeremy Cloud UFER only ok to cover
Electrical Rough-In9/18/20199/19/20199/19/2019PPASS
DetailsJames Ady
Maz Phone #: ###-#### Underground to light pole and pole bases ok to cover