Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberELE20-02497
StatusIssued
Name SOLAR CASCADE
Site Address 1032 S BROADWAY AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Wiring of barber shop per plans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In8/5/20208/5/20208/5/2020PPASS
DetailsEric Story
Corrections fixed- Wall only ok to cover
Electrical Rough-In8/5/20208/5/20208/5/2020PFAIL
DetailsEric Story
Code 9481. Walls only Phone #: ###-#### Inspection requested via web by Dave Brueggemann
Corrections not fixed MC not replaced as MARKED on metal stud on previous inspection-If not fixed re-inspection fee to be added
Electrical Rough-In8/3/20208/4/20208/4/2020AFAIL
DetailsJames Ady
walls only Phone #: ###-#### Inspection requested via web by Dave Brueggemann 11o.3B Insulated bushings shall be installed on MC a per instructions. 330.24 MC Bent to breaking point(Next to back door.) 300.4 MC shall not be secured within 1 1/4in from face of framing(Water heater and recep back office) 110.12 Opening shall be closed(Missing conduit or KO seal Hall 4 gang.) MC not completed to floor box junction point.
Electrical Rough-In7/20/20207/21/20207/21/2020APASS
DetailsRock A. Hudson
Underground only Phone #: ###-#### Inspection requested via web by Dave Brueggemann City approved set pf prints on site confirmed. Under slab rough in ok cover