Permit Information
Permit NumberFIR14-00252
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1000 W MYRTLE ST
Project NameJUMP Kitchen Lobby Areas
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of connecting to the existing below grade feed main. Extend the new wet system piping to the above grade kitchen studio and lobby areas for levels 1 and 2. Areas shall be protected for light and ordinary hazards, utilizing extended coverage and standard sprinklers.

(JUMP - JACK'S URBAN MEETING PLACE - ABOVE GRADE TENANT IMPROVEMENT) - To finish for occupancy a 240,445 sq. ft., six story social meeting and education building with a four level parking garage. The first floor consists of parking on the south, a driveway and circulation areas, the fire command center, an entry lobby on the south with a kitchen and seating area, restrooms, storage and mechanical areas. There are also some building storage, mechanical, trash and sprinkler rooms. The second floor consists of administrative offices and restrooms above the entry lobby. The third floor contains a level of parking on the south, circulation and egress areas, an outdoor garden studio, as well as, building storage, maintenance and sprinkler rooms. The fourth floor has a parking garage level with a dust containment room along with electrical and storage rooms. There are circulation and egress areas with a terrace and public restrooms. There is an Inspiration Studio and a Multi Media Studio. The fifth floor has a Sculpture Garden at the top of the parking garage. Within the Sculpture Garden there is a Makers Studio, a party area with a trellis cover and a kitchen. There are also circulation and egress areas with a large entry lobby, outdoor seating area, public restrooms, a Movement Studio and a Multi-Purpose Studio. At the center is the Jump Room Studio. The sixth floor has a large Sky Lobby, circulation and egress areas and two terraces. At the center is the Pioneer Grand Ballroom with a catering kitchen. There are mechanical equipment wells at a portion of the roof area. The construction of all exterior circulation and egress areas, exterior stairways, elevators and mechanical shafts and the completion of all mechanical, electrical and machine rooms were done under the shell permit BLD13-00016. All construction per the approved plans and attached comment list. This high-rise building is fully fire sprinklered with an approved fire alarm system. Separate Fire Protection permits will be required for the necessary fire protection modifications; as regulated by the Fire Department. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/6/20158/7/20158/7/2015APASS
DetailsThomas Walsh
Final inspection for kitchen and lobby area.
Need calc placard installed. Otherwise, past final inspection.
INSP-Supply line flush8/5/20158/6/20158/6/2015APASS
DetailsThomas Walsh
Waterflow tests of the wet system risers for the first floor and second floor litchen and lobby areas. Both systems activated alarm system within 30 seconds.
INSP-Sprinkler Rough-in/Hydro5/21/20155/22/20155/22/2015APART
DetailsThomas Walsh
Hydrotest of first floor kitchen and lobby system - 200 psi @ 2 hours - PASSED
NOTE: 2nd floor tested OK yesterday.
INSP-Sprinkler Rough-in/Hydro5/20/20155/21/20155/21/2015APART
DetailsThomas Walsh
Hydrotest of 2nd floor kitchen and lobby area - Passed. First floor system had leak so that one will be retested at a later date.
INSP-Sprinkler Rough-in/Hydro5/18/20155/19/20155/19/2015ACANC
DetailsThomas Walsh

Found leak in the kitchen system - inspection cancelled
INSP-Sprinkler Rough-in/Hydro5/12/20155/13/20155/16/2015PPASS
DetailsThomas Walsh
Kitchen rough-in inspection for levels 1 and 2
INSP-Sprinkler Rough-in1/28/20151/28/20151/28/2015PPART
DetailsForrest France
Rough-in for cover finished at the 1st floor kitchen lobby area, okayed SW coverage adjacent to the fireplace. Noted cold solder issues at sprinklers each side of beam pockets.
INSP-Sprinkler Rough-in1/21/20151/22/20151/22/2015PPART
DetailsForrest France
Preliminary inspection for the 3rd floor parking garage level completed. Dry pendents at the hard lid ceiling south side central okayed for cover.
INSP-Sprinkler Rough-in1/21/20151/22/20151/21/2015PCANC
DetailsForrest France
This an OH/RTC inspection. Mike S is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in8/6/20148/7/20148/7/2014APART
DetailsForrest France
Overhead rough-in okay for cover at the 4th floor innovation room sheetrock ceilings and the multi-media room. Noted one damaged pendent sprinkler to be replaced.
INSP-Sprinkler Rough-in/Hydro8/1/20148/4/20148/4/2014ACANC
DetailsForrest France
Please call 45 mintures prior to inspection. Leroy is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in7/23/20147/25/20147/25/2014APART
DetailsScott Arellano
Cover approved at levels one and two only in the specific lobby areas as discussed, and restrooms .