Information based on query as of Tuesday, May 21, 2024.
Permit Information
Permit NumberFIR14-00687
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1004 W ROYAL BLVD
Project NameRivers Edge Apartments
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of (2) dry systems and (1) wet system to protect the 1st floor parking garage, offices and recreation areas. Floors 2-5 plus the attic dry systems will be submitted at a later date under a separate permit.

Note: None of the standpipe system was reviewed at this time. The standpipe will be reviewed at a later date when the entire standpipe system has been submitted.

The underground piping was reviewed under FIR14-00638

(RIVER EDGE APARTMENTS - GARAGE) (x-ref expired permit BLD12-00318) To construct a 97,150 sq. ft. mixed use occupancy parking garage / common activity area. The parking area is 84,390 sq. ft. plus approx. 12,760 sq. ft. common & activity support area. Approximately 69,800 sq. ft. of the 1st level parking / common area is covered by a reinforced, post tensioned, 3-hour fire rated, horizontal concrete floor assembly acting as a horizontal fire separation between the four stories of residential units above. The installation of an NFPA 13 fire sprinkler system is required throughout this building and is used for allowable area increase and for an additional story. All construction shall be per the approved plans, red-lined notes and all attached plan reviewer's comments / conditions reports. drs DRH12-00013, CUP11-00090, CFH11-00036 & associated with BLD12-00319 & BLD12-00320
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/14/20159/15/20159/15/2015APASS
DetailsThomas Walsh
Test of new control valve for horizontal exit standpipes. Also signed off Certificate of Completion forms.
INSP-Final Inspection8/19/20158/20/20158/20/2015PCANC
DetailsThomas Walsh
Revised plans for this permit have been submitted to Tim Frost for review prior to final sign off. Contractor will request final sign off after this review is completed.
INSP-Final Inspection8/14/20158/14/20158/14/2015PPART
DetailsThomas Walsh
Completed 24 hour air tests of the two dry pipe valves for the parking garage. PASSED
INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015PPART
DetailsThomas Walsh
Rough to cover inspection for 5th floor corridors - both north and south wings.
OK to cover pipe in this area.
Also Hydrostatic pressure test of the two (2) dry-pipe systems for the parking garage, and the wet system for the first floor leasing offtice area. - PASSED.
Also hydrotest of the wet systems for floors 3 and 4 - noth and south sides - PASSED
INSP-Sprinkler Rough-in8/10/20158/10/20158/10/2015PPART
DetailsThomas Walsh
RTC inspection for the dry ppe fire sprinkler system protecting the east-side of the parking garage. Except for two (2) heads that need to be added - one on the east entry rollup gate and the other at the south-west corner of the system, it is OK to cover the pipe for this system.
Will reinspect to ensure that these 2 sprinklers get installed prior to hydrotest.
INSP-Sprinkler Rough-in/Hydro8/4/20158/4/20158/4/2015PPART
DetailsThomas Walsh
RTC inspection for west dry system in parking garage. Need to add 4 DP heads in south west corner. Otherwise OK to cover the pipe for this system.
INSP-Sprinkler Rough-in7/15/20157/17/20157/17/2015APART
DetailsThomas Walsh
RTC inspection for first floor wet-pipe system protecting the office area - hard lid areas.
OK to cover pipe in this area.
INSP-Sprinkler Rough-in6/25/20156/26/20156/26/2015ACANC
DetailsThomas Walsh
Wrong permit for this day's inspection. See FIR14-00096 for inspections completed today (6/26).
INSP-Sprinkler Rough-in5/19/20155/20/20155/20/2015PPART
DetailsThomas Walsh
Hard lid inspection for pool room. See plans for a/s inspected.
INSP-Sprinkler Rough-in1/20/20151/20/20151/20/2015APART
DetailsForrest France
Intended for 5th floor wet system.
INSP-Sprinkler Rough-in1/14/20151/15/20151/16/2015PPART
DetailsForrest France
OH cover inspection completed for the 5th floor soffit lower lid ceilings at room units 530-537 tower one.