Permit Information
Permit NumberFIR14-00781
StatusFinaled
Name ALARMCO
Site Address 2800 W CHERRY LN
Project NameOak Park Bldg K Replace FACP
Customer Number 
ePlanReviewYes
Description
To replace a faulted fire alarm system with a new SK5208 in an temperature controlled NEMA enclosure. Installation of a smoke det. to protect FACP and relocation of pull stations to current mounting height code req. Re-use of existing code compliant bedroom sounders. Not associated with a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/4/20153/5/20153/5/2015APASS
DetailsForrest France
Final inspection completed, verified finishes. Fire alarm permit finaled.
INSP-Final Inspection2/5/20152/11/20152/11/2015APART
DetailsForrest France
Functional testing completed satisfactory. Items needed prior to final include; replace damaged HD at the panel enclosure, provide knox box per plan review note #9, remove "local alarm only" signage at the manual pull stations.
INSP-Final Inspection1/22/20151/27/20151/27/2015AFAIL
DetailsForrest France
Manual pull stations need relocated as indicated per the project scope and plan review comment #19, provide knox box per review note #9.
INSP-Final Inspection1/19/20151/22/20151/22/2015ADEFR
DetailsForrest France
Final Inspection for Panel Change Out and Phone Line Monitoring Phone #: ###-#### Inspection requested via web by Jeremy Berg