Permit Information
Permit NumberFIR14-00783
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1600 W GOWEN RD
Project NameSkyWest Maintenance Hangar Fac
Customer Number 
ePlanReviewYes
Description
Quick Permit
To install approximately 183' of 12",16", and 18" C905 pvc fire service line

(SkyWest Maintenance Hangar - Grading/Drainage only) Permit to excavate, grade and compact site earth materials in preparation for a future aircraft maintenance hangar building. Install curb, gutter, paving, striping and landscaping as approved by the Public Works and Planning & Zoning Departments. Underground site utilities are included in this scope of work. No buildings or footings are to be constructed under this permit. // leg
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/11/20158/11/20158/11/2015PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro6/22/20156/22/20156/22/2015PPASS
DetailsTroy Cobbley
Underground hydro from the backflow at the tank to the inside riser passed.
INSP-Supply line flush5/26/20155/27/20155/27/2015APASS
DetailsJim Page
Underground flush complete.
INSP-Sprinkler Rough-in/Hydro5/19/20155/20/20155/20/2015APASS
DetailsTroy Cobbley
The underground hydro from the United Water outlet to the first coupling above the floor is passed.
INSP-Sprinkler Rough-in/Hydro4/10/20154/13/20154/13/2015ANR
DetailsKatie Marron
Not ready per phone call with contractor.
INSP-Sprinkler Rough-in3/19/20153/20/20153/20/2015APART
DetailsForrest France
Inspection for thrust blocking completed satisfactory- okay to cover at areas installed to date.
INSP-Sprinkler Rough-in3/17/20153/18/20153/18/2015APART
DetailsForrest France
Inspection for end caps at manifold and ductile risers/90's at tank supply and draft piping. Thrust blocking is not yet provided. Photo documentation recorded.
INSP-Sprinkler Rough-in3/5/20153/5/20153/6/2015PPART
DetailsForrest France
Inspection for the extent of UG manifold work completed to date including three 18" x 16" tees, approx. 25' of 18" supply pipe, visual internal inspection of piping. Discussed project schedule, remainder of work etc.
INSP-Sprinkler Rough-in2/9/20152/9/20152/9/2015PPART
DetailsForrest France
Inspection for hangers only at z-purlins prior to cover.
INSP-Sprinkler Rough-in1/22/20151/23/20151/23/2015APART
DetailsForrest France
Inspection for hanger attatchments at the riser room prior to vapor cover.
INSP-Sprinkler Rough-in1/22/20151/22/20151/22/2015PPART
DetailsForrest France

INSP-Sprinkler Rough-in11/3/201411/3/201411/3/2014APART
DetailsForrest France
Ref. dated plan annotations for areas inspected.
INSP-Sprinkler Rough-in10/31/201410/31/201410/31/2014PPASS
DetailsCraig D. Hanson
underground stub
INSP-Sprinkler Rough-in10/30/201410/30/201410/30/2014PPART
DetailsForrest France
Ref. to stamped plans for portions okayed for bury.
INSP-Sprinkler Rough-in10/29/201410/30/201410/30/2014APART
DetailsForrest France
UG fire supply line ductile risers and stubs to a point approx. 15' beyond the stem wall as marked/dated on approved plans okayed for bury.