ePlanReviewYes
Description
The fire sprinkler scope of work consists of providing protection for a 3 level multi family dwelling. There are three building separated by firewalls. The buildings are adjoining. Two of the buildings are protected using NFPA 13R. The southeast building is protected using NFPA 13. There is a class 1 standpipe on the intermediate floor landing with one roof outlet. Each level has floor level control valves. The majority of the building above grade levels utilize residential sprinklers.

The parking garage is under permit FIR14-00478

The associated building permits to this project are BLD14-00772, BLD14-01936, BLD14-01937, BLD14-01938 and BLD14-02406

BLD14-01937 West Sherwood Apartments - Building 1 - To construct a 41,670 square foot, three story, wood framed apartment building. This building contains 57 living units. This building is being constructed on a three-hour fire-resistive concrete podium above a one-story concrete parking garage building. This apartment building is being divided into three buildings by two firewalls. This building is being sprinklered with an NFPA 13R system
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/20/20157/21/20157/21/2015PPASS
DetailsThomas Walsh
Trip test of the dry pipe valve, including the new accelerator - tested OK within 45 seconds.
Fire sprinklers for the entire project have been tested with fire alarm interface. Inspection with final walk through needs to be conducted prior to final sign-off, including obtaining ROCs. Systems are to remain in service from this point on.
INSP-Final Inspection7/16/20157/17/20157/17/2015PPART
DetailsThomas Walsh
Test/inspection of all fire sprinkler systems (dry and wet) and interface with fire alarm system, including tampers, waterflows, low-air f/ dry system, sectional control valves, and a trip test of the dry pipe valve protecting the parking garage.
All devices tested OK and within time requirements, except the dry pipe valve that only delivered water within 90 seconds trip test. Therefore an accelerator device will be required on this system to get below the 60 second time requirement.
INSP-Sprinkler Rough-in/Hydro7/16/20157/16/20157/16/2015PPASS
DetailsThomas Walsh
Hydrostatic pressure test of all the wet pipe systems for the above parking garage areas, including each floor of the residential building, and the clubhouse. (5 total wet systems).
All tested at 200 psi @ 2hrs - All passed.
INSP-Sprinkler Rough-in/Hydro7/15/20157/16/20157/16/2015ACANC
DetailsThomas Walsh
Wrong permit # called in for this inspection - See permit FIR 14-00628 for inspection/test conducted this visit.
INSP-Sprinkler Rough-in5/20/20155/21/20155/21/2015ACANC
DetailsThomas Walsh
Wrong permit number requested.
INSP-Sprinkler Rough-in5/13/20155/13/20155/16/2015PPASS
DetailsThomas Walsh
Clubhouse rough-in inspection. No discrepancies noted.
INSP-Sprinkler Rough-in4/15/20154/16/20154/16/2015APART
DetailsKatie Marron
Tenting at 4th flr at south end completed with the exception of rm 431 (not completed) and the exterior wall in shower enclosure at rm 432. One area in room 430 adjusted on site.
INSP-Sprinkler Rough-in4/8/20154/9/20154/9/2015APASS
DetailsTim Frost
Passed

However, I had a conference with the super. I told him there could be a potential problem with freeze ups where the insulation butts together directly above the sprinkler piping.
INSP-Sprinkler Rough-in3/26/20153/27/20153/31/2015PPART
DetailsForrest France
Completed rough-in inspection for the remainder of the 4th floor living units only as noted on stamped plans. Items noted include; overspaced coverage at unit 405, missing coverage at units 430 and 432. Need to install flushing caps per plan notes.
INSP-Sprinkler Rough-in3/18/20153/19/20153/20/2015APART
DetailsForrest France
2nd floor west side living unit soffits only.
INSP-Sprinkler Rough-in3/10/20153/12/20153/12/2015APASS
DetailsTroy Cobbley
Requesting RTC inspection on the 3th floor. See the city approved plans for rooms marked with "ok" and todays date where rough-in has passed.
INSP-Sprinkler Rough-in3/10/20153/11/20153/11/2015APASS
DetailsTroy Cobbley
Inspection on the 4th floor was just for the general rough-in, not all drops or heads are installed. No tenting has been performed. Only apartments were looked at and not the hallway. City approved plans marked.
INSP-Sprinkler Rough-in2/26/20152/27/20153/6/2015APART
DetailsForrest France
Inspection to be on the 3rd floor. Jeremiah is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in2/25/20152/26/20152/26/2015ACANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in2/19/20152/20/20152/20/2015APART
DetailsForrest France
Partial rough-in for branchlines installed at the 3rd floor west side living units. Min. distance between heads is exceeded at five rooms -323,321,314,312,311 and 2nd floor 212. Drops are not yet installed at some locations.
INSP-Sprinkler Rough-in2/18/20152/19/20152/19/2015PPART
DetailsForrest France
Rough-in inspection completed for the remainder of the 2nd floor living units. Also verified previous C/N items.
INSP-Sprinkler Rough-in2/13/20152/18/20152/18/2015APART
DetailsForrest France
Completed initial rough-in for the 2nd floor living units as annotated on approved plans. Items incude; missing sprinker at closet, overspaced coverage, sprinkler too close to ceiling fan, noted two unprotected concealed spaces, incorrect type of head at the janitors room.
INSP-Sprinkler Rough-in/Hydro2/13/20152/17/20152/17/2015APART
DetailsForrest France
This inspection will be on the 2nd floor. Jeremiah R is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### Inspection requested via web by Stan Beus