INSP-Final Inspection | 7/24/2020 | 7/29/2020 | 7/28/2020 | A | CANC |
Jim Page
|
|
|
Please call Mike 1 hr before arriving. Phone #: ###-#### >> Inspection requested via web by James Williams Inspection cancelled from web by: James Williams
|
INSP-Final Inspection | 7/24/2020 | 7/28/2020 | 7/28/2020 | A | FAIL |
Jim Page
|
|
|
Smoke detectors located farther than 60 inches away from doors with mag holders, smoke detectors must comply with 17.7.5.6 of NFPA72. 2 areas have audio visual notification exceeding 15 feet from end of corridor. Notatyed tenat space where a 30cd should have been provided but device was set at 15. Inspection was stopped due too defeciencies.
Please call Mike 1 hr before arriving. Phone #: ###-#### Inspection requested via web by James Williams
|
INSP-Final Inspection | 7/20/2020 | 7/24/2020 | 7/24/2020 | A | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, request will be rescheduled for a later date.
Please Give Mike a call 1 hour prior to arrival. Phone #: ###-#### Inspection requested via web by James Williams
|
INSP-Final Inspection | 7/20/2020 | 7/23/2020 | 7/23/2020 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with point of contact, demo work done by others in suite 186 without permits, due too demo work troubles are on the panel. Instructed GC with RRC for space 186 the proper requirements prior to demo work.
Please Give Mike a call 1 hour prior to arrival. Phone #: ###-#### Inspection requested via web by James Williams
|
INSP-Final Inspection | 3/17/2020 | 3/20/2020 | 3/20/2020 | A | FAIL |
Jim Page
|
|
|
Numerous walls have been added in one of the tenant spaces, TI is marked on city approved drawings. Wall layout affects audio visual coverage, floor plan must match approved drawings, inspection was stopped.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Alarm Testing | 10/29/2019 | 10/31/2019 | 10/31/2019 | A | PART |
Jim Page
|
|
|
Fire alarm inspection/testing for suite 180 is complete.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Alarm Testing | 10/28/2019 | 10/29/2019 | 10/28/2019 | A | CANC |
Jim Page
|
|
|
Needs to be done at 7:00am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
INSP-Alarm Testing | 10/25/2019 | 10/28/2019 | 10/28/2019 | A | FAIL |
Jim Page
|
|
|
Sounder base and A/V devices do not sync during operation. Pull station in 180 tenant space did not operate when activated.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Alarm Testing | 10/23/2019 | 10/25/2019 | 10/25/2019 | A | FAIL |
Jim Page
|
|
|
Relocate 2 smoke detectors that are overspaced. Relocate smoke detector that is to close to HVAC register or relocate HVAC register to get minimum of 36 inches away. Sync sounder base to A/V devices in space, sound did not sync.
Needs done at 7:00 am Phone #: ###-#### Inspection requested via web by Sam Ball
|