INSP-Final Inspection | 4/15/2020 | 4/15/2020 | 4/15/2020 | P | PASS |
Jim Page
|
|
|
Annunciator location has been updated and approved on the city approved drawings, final inspection is complete.
|
INSP-Final Inspection | 3/31/2020 | 4/3/2020 | 4/3/2020 | A | PART |
Jim Page
|
|
|
Backup power for internet monitoring has been verified, plans still show annunciator inside of building instead of vestibule, permit can be finaled after plans show annunciator in its current location.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 2/25/2020 | 2/27/2020 | 2/27/2020 | P | FAIL |
Jim Page
|
|
|
Annunciator is installed in a different location than what is shown on the city approved drawings. Fire system is being monitored by internet, associated components for monitoring/emergency power need to be submitted and approved prior to final sign off.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|