INSP-Final Inspection | 6/22/2020 | 6/22/2020 | 6/22/2020 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection is complete, irrigation shut-down on flow switch activation witnessed during water flow.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 6/19/2020 | 6/19/2020 | 6/19/2020 | P | CANC |
Jim Page
|
|
|
Final fire sprinkler inspection cancelled per conversation with point of contact, irrigation shutdown on flow switch activation not installed, inspection will be rescheduled for a later date.
Ready any time, call James before heading up Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 6/19/2020 | 6/19/2020 | 6/19/2020 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Overhead Hydro before Final, call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 3/10/2020 | 3/11/2020 | 3/11/2020 | A | PASS |
Jim Page
|
|
|
Previously noted item has been corrected, cover is approved, sticker placed approval.
Tenting inspection. Call Anthony before heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 3/4/2020 | 3/4/2020 | 3/4/2020 | P | FAIL |
Jim Page
|
|
|
Minimum R38 not met at time of install.
As Built approved and insulation complete. Call Anthony before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 2/13/2020 | 2/13/2020 | 2/13/2020 | A | PART |
Jim Page
|
|
|
Rough in inspection for overhead fire sprinkler piping is complete, piping between conditioned spaces approved for cover, tenting inspection to be completed at a later date, piping requiring freeze protection is not approved for cover, as-builts to show minor changes to piping due too structural beams.
Rough to cover. Call Anthony when headed out. He has an inspection with Troy at 8am on another project. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|