INSP-Final Inspection | 6/4/2020 | 6/5/2020 | 6/5/2020 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection is complete. Irrigation shutdown during flow switch activation observed.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
INSP-Sprinkler Rough-in/Hydro | 6/4/2020 | 6/5/2020 | 6/5/2020 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed at city pressure, no pressure loss observed at riser provided gauge.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
INSP-Sprinkler Rough-in | 4/6/2020 | 4/7/2020 | 4/7/2020 | A | PASS |
Jim Page
|
|
|
Tenting has been corrected, all tenting in place at time of inspection, cover is approved. Cover sticker has been placed.
tenting re-inspection Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
INSP-Sprinkler Rough-in | 4/5/2020 | 4/6/2020 | 4/6/2020 | A | FAIL |
Jim Page
|
|
|
Tenting not installed correctly in numerous areas, pocket between sheetrock and piping will be compromised, cover is not approved. Second failure for same item, a re-inspection fee has been attached.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
INSP-Sprinkler Rough-in | 4/1/2020 | 4/3/2020 | 4/3/2020 | P | FAIL |
Jim Page
|
|
|
Plastic sheeting used for tenting, numerous areas where the pocket between sheetrock and piping is compromised.
Tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
INSP-Sprinkler Rough-in | 3/26/2020 | 3/27/2020 | 3/27/2020 | P | PART |
Jim Page
|
|
|
Previously noted item has been corrected, no tenting installed at time of inspection, cover is not approved.
Verify missing head has been installed in open Tee Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
INSP-Sprinkler Rough-in | 3/19/2020 | 3/20/2020 | 3/20/2020 | P | FAIL |
Jim Page
|
|
|
Open outlet above finish ceiling with no sprinkler drop, area was notated on city approved drawings. No tenting installed at time of inspection.
Johnathon Phone #: ###-####
|