INSP-Final Inspection | 4/20/2020 | 4/21/2020 | 4/21/2020 | A | PASS |
Jim Page
|
|
|
Final inspection for commercial hood fire suppression activation complete.
Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
INSP-Final Inspection | 4/17/2020 | 4/20/2020 | 4/20/2020 | A | FAIL |
Jim Page
|
|
|
Same issue as last inspection, Make-up air did not function creating too much negative pressure for proper egress on exit door, required more force to open than IFC allows, a re-inspection fee has been added to permit due too 2 failures on permit. Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
INSP-Final Inspection | 4/16/2020 | 4/17/2020 | 4/17/2020 | A | FAIL |
Jim Page
|
|
|
Make-up air did not function creating too much negative pressure for proper egress on exit door, required more force to open than IFC allows.
Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
INSP-Final Inspection | 4/13/2020 | 4/14/2020 | 4/14/2020 | A | CANC |
Jim Page
|
|
|
Make-up air for hood not operational according to point of contact, this request is cancelled per conversation with point of contact.
Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
INSP-Final Inspection | 4/10/2020 | 4/13/2020 | 4/13/2020 | A | CANC |
Jim Page
|
|
|
Gas meter was not placed, could not test gas shutdown on activation. Inspection will be rescheduled for a later date, this request is cancelled per conversation with point of contact.
Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|