Permit Information
Permit NumberNAF15-00001
StatusFinaled
Name RON LARSON
Site Address 500 W CURLING DR
Project NameCRAN CREEK-TENNIS EXPANSION
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of 6”x180’ C-900 underground piping through a 4” backflow preventer, to a 4” riser to supply a 4”x2½”x1¼” grid.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final5/13/20155/14/20155/14/2015PPASS
DetailsKatie Marron
Scope of work completed satisfactory. Permit finaled.
INSP-Sprinkler Rough-in/Hydro4/30/20155/1/20155/1/2015PPART
DetailsKatie Marron
Hydrostatic test completed satisfactory. Completed rough-in inspection. Verified seismic bracing, retaining straps and riser/aux drain complete.
INSP-Supply line flush4/16/20154/20/20154/20/2015PPART
DetailsKatie Marron
Underground supply flush completed satisfactory.
INSP-Supply line flush4/14/20154/15/20154/15/2015AFAIL
DetailsKatie Marron
Insufficient means provided to complete flushing.
INSP-Sprinkler Rough-in/Hydro4/7/20154/8/20154/9/2015PNR
DetailsForrest France
Missing siesmic bracing, retaining straps, tie-ins. Riser and aux. drain incomplete at this time. Partial inspection only. Per Forrest France.
INSP-Supply line flush4/7/20154/8/20154/9/2015PFAIL
DetailsForrest France
Provide sufficient method to complete flushing per NFPA 13. Inspection completed per Forrest France
INSP-Sprinkler Rough-in/Hydro1/28/20151/28/20151/28/2015APART
DetailsForrest France
UG fire supply line okayed for cover per inspection completed by T. Cobbley 1/27 at the initial visit for the hydrostatic test.
INSP-Sprinkler Rough-in/Hydro1/26/20151/27/20151/27/2015APART
DetailsForrest France
UG fire supply line hydrostatic test completed.
INSP-Sprinkler Rough-in/Hydro1/20/20151/26/20151/26/2015PCANC
DetailsForrest France
Call prior to going Phone #: 2087619666 >> Inspection requested via mobile web by Ron Larson Inspection cancelled via mobile web on Monday, January 26, 2015.