INSP-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/7/2019 | 2/11/2019 | 2/11/2019 | P | FAIL |
Troy Cobbley
|
|
|
Need to have access to verify the insulation has been installed since the ceiling were put in.
Contact Leroy Anderson ###-#### 30 min prior to Fire Final start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Scott Carter II
|
INSP-Sprinkler Rough-in | 1/3/2019 | 1/4/2019 | 1/4/2019 | P | PART |
Troy Cobbley
|
|
|
Rough-in passed but piping can not be covered until the barrier above the ceiling has been repaired/re-installed. One head in a corridor needs to be re-located to match plans and will be checked at the next inspection.
Please contact Brad Westbrook 30 mins prior inspection. Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 1/2/2019 | 1/4/2019 | 1/3/2019 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 12/26/2018 | 12/27/2018 | 12/27/2018 | A | PASS |
Troy Cobbley
|
|
|
Piping in the two rooms that have been marked "ok" can be covered. I spoke to Leroy about the large note that if any ceiling exceed 10' then plan modifications will be needed.
rough to cover for sheet rock // Austin Phone #: ###-####
|
Sprinkler Plan Check | 12/17/2018 | | 12/17/2018 | | PASS |
Mark Stumbaugh
|
|
|
All ceilings to be 10'-0" or lower, or revised hydraulic calculations will be required
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/17/2018 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 12/17/2018 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 12/17/2018 | | DONE |
|
|
|
|
Application received | | | 12/5/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 5 2018 8:35AM
|
Plan assigned to (Tim) | 12/5/2018 | | 12/5/2018 | | DONE |
Mark Stumbaugh
|
|
|
|
Intake Approval | | | 12/5/2018 | | PASS |
Tim Frost
|
|
|
|