First Notice | 6/20/2019 | 6/20/2019 | 8/1/2019 | | DONE |
Brian Scoles
|
|
|
This permit finaled on the web by Dan Flaherty
|
Final | 6/19/2019 | 6/20/2019 | 6/20/2019 | A | PASS |
Brian Scoles
|
|
|
Final inspection ; Jake is your contact. Thank you! Phone #: ###-#### Inspection requested via web by Kim Adams- final ok- card signed
|
Rough-in | 4/23/2019 | 4/24/2019 | 4/24/2019 | A | PASS |
Brian Scoles
|
|
|
grid in the locker rooms for approval for cover ; Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- R/I o9k- ok for ceiling tiles
|
Rough-in | 4/22/2019 | 4/23/2019 | 4/23/2019 | A | FAIL |
Brian Scoles
|
|
|
Approval for cover on the locker room area. Jake is your contact. Thank you! Phone #: ###-#### Inspection requested via web by Kim Adams- need to finish insulation tape seams in main corridor- all joints not done
|
Rough-in | 3/21/2019 | 3/21/2019 | 3/21/2019 | A | PART |
Brian Scoles
|
|
|
Final inspection kitchen ; hood Phone #: ###-#### Inspection requested via web by Kim Adams- TCO for caffateria and kitchen only ok
|
Final | 3/19/2019 | 3/20/2019 | 3/20/2019 | P | PART |
Brian Scoles
|
|
|
the kitchen and cafeteria - Jake is your contact. Thank you Phone #: ###-#### Inspection requested via web by Kim Adams- all equipment under class 1 hoods needs to be set into place with clearances required- caffeteria, kitchen and roof ok- airbalance report ok-
|
Final | 3/13/2019 | 3/14/2019 | 3/14/2019 | A | PART |
Brian Scoles
|
|
|
I need a final, temp c of o in the kitchen and rough in inspection in the locker rooms. Jake is your contact. Thanks Phone #: ###-#### Inspection requested via web by Kim Adams- need to extend flues on 2 units on roof 3 feet above intake- need 1500 degree gasket on both class 1hood exhaust fans- need to pan off 2 transfers above ceiling to kitchen- need all equipment set under both class 1 hoods and class 2 hood needs dishwasher installed in center- need air balance report for both class 1 hoods and 1 class 2 hood and MAU- R/I in locker rooms ok- ok to cover- 2 ceiling heaters NW entry ok- storage room in kitchen area ok to cover
|
Rough-in | 2/28/2019 | 3/1/2019 | 3/1/2019 | A | PART |
Brian Scoles
|
|
|
RI inspection for ceiling cover in the kitchen at fairmont for tomorrow. Contact Jake Johnstone ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty- ceiling grid in kitchen area and bathrooms ok- need to see storage room in kitchen when grid is installed- class 1 hood and class 2 hoods ok- ok for ceiling tiles excluding storage room
|
Rough-in | 2/22/2019 | 2/25/2019 | 2/25/2019 | A | PART |
Brian Scoles
|
|
|
locker rooms for approval for duct wrap. Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- locker rooms seal on duct ok- ok for insulation- call in dishwasher hood when installed
|
Final | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | CANC |
Brian Scoles
|
|
|
final inspection in the kitchen hood . Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- should have been R/I inspection
|
Rough-in | 2/22/2019 | 2/22/2019 | 2/22/2019 | A | PASS |
Brian Scoles
|
|
|
final inspection in the kitchen hood . Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- fire wrap both drops and pants to hood ok- insulation all duct kitchen area ok- ok for grid kitchen area only
|
Rough-in | 2/13/2019 | 2/14/2019 | 2/14/2019 | A | PASS |
Brian Scoles
|
|
|
Rough in for kitchen hood. Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- north and south grease ducts ok for firewrap- will need remaining R/I inspections scheduled when ready
|
Rough-in | 2/12/2019 | 2/13/2019 | 2/13/2019 | A | PART |
Brian Scoles
|
|
|
Inspection of weld for kitchen hood. Jake is your contact. Thank you! Phone #: ###-#### Inspection requested via web by Kim Adams- north grease duct welds in 4 locations ok- south grease duct missing welds east side above pants rest is good- rerschedule when ready
|
Rough-in | 2/4/2019 | 2/5/2019 | 2/5/2019 | A | PART |
Brian Scoles
|
|
|
for ceiling cover inspection in the kitchen/ bathroom hard lids Phone #: ###-#### Inspection requested via web by Kim Adams- insulation on supply, return and make up air in kitchen only ok- all hard lid ceilings for bathrooms and kitchen area only ok to cover- still need light test on grease duct called in when ready
|
Rough-in | 1/30/2019 | 1/31/2019 | 1/31/2019 | A | PASS |
Chad Schwendiman
|
|
|
Grease duct light inspection at TML shop 120 E 40th street Steve Beason is the contact ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Light test pass for 2 ea. straight drops, and 2 ea. pair of duct pants
|
Rough-in | 1/28/2019 | 1/29/2019 | 1/29/2019 | A | PART |
Brian Scoles
|
|
|
Kitchen for duct wrap. Jake is your contact. Thank you Phone #: ###-#### Inspection requested via web by Kim Adams- seal on duct in kichen area supply return and make up ok- ok to insulate
|
Issue PAID IN FULL permit | | | 11/21/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/21/2018 | | DONE |
|
|
|
This permit was created on the web by Kim Adams
|