Final | 3/2/2020 | 3/3/2020 | 3/3/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Dave Sorensen- final ok
|
Final | 3/1/2020 | 3/2/2020 | 3/2/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Dave Sorensen 1- need city approved man j onsite none found 2- need locking caps on a/c service ports 3- need to complete duct blast test and have paper work onsite
|
Pressure Test | 12/11/2019 | 12/12/2019 | 12/12/2019 | A | PASS |
Brian Scoles
|
|
|
60lb test on gas supply piping to aud. Gas reg installed inside of building in attic on west side of Aud. Phone #: ###-#### Inspection requested via web by Dave Sorensen- 60lb gas pass from meter underground to regulator in building attic- tagged this gas line at meter- ok to cover
|
Rough-in | 12/12/2019 | 12/12/2019 | 12/12/2019 | A | PASS |
Brian Scoles
|
|
|
60lb test on gas supply piping to aud. Gas reg installed inside of building in attic on west side of Aud. Phone #: ###-#### Inspection requested via web by Dave Sorensen- R/I ok- regulator installed in attic
|
Rough-in | 12/11/2019 | 12/11/2019 | 12/11/2019 | P | PART |
Brian Scoles
|
|
|
Rough in inspection on duct system - manuals on site - will be testing gas supply line to aud to 60llbs at a later date. Phone #: ###-#### Inspection requested via web by Dave Sorensen- R/I will pass once regulator is installed in attic and inspected- ok to cover walls only at this time- check equipment at final not set on R/I- still need 60lb gas test witnessed when ready- will need duct blast and air balance at final
|
Rough-in | 12/5/2019 | 12/6/2019 | 12/6/2019 | P | FAIL |
Chad Schwendiman
|
|
|
gas pressure and flue test also Phone #: ###-#### Inspection requested via web by Dave Sorensen - No approved manual J onsite. Gas piping from house to ADU is undersized. Need to increase pipe size or increase gas pressure. If choice is to increase gas pressure all piping from meter to regulators will need to be test at 60lbs on a 100lb gauge.
|
Pressure Test | 12/6/2019 | 12/6/2019 | 12/6/2019 | P | PART |
Chad Schwendiman
|
|
|
gas pressure and flue test also Phone #: ###-#### Inspection requested via web by Dave Sorensen - 5lb flue pass, 20lb gas pass for piping inside of ADU. Gas piping from house to ADU is undersized. Need to increase pipe size or increase gas pressure. If choice is to increase gas pressure all piping from meter to regulators will need to be test at 60lbs on a 100lb gauge.
|
Issue PAID IN FULL permit | | | 12/4/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/4/2019 | | DONE |
|
|
|
This permit was created on the web by Dave Sorensen
|