BLD-Energy code compliance | 6/17/2020 | 6/17/2020 | 6/17/2020 | A | PASS |
Tell Riley
|
|
|
Inspection requested via web by Carl Funk//ok per plans, add VB over window headers//framing ok per plans, changes in engineering and verbal walk through with engineer based on the first 8 units//
|
BLD-Framing/Rough-in | 6/12/2020 | 6/12/2020 | 6/12/2020 | A | PART |
Tell Riley
|
|
|
Inspection requested via web by Carl Funk//ok to insulate//see Joey onsite for correction notes//
|
BLD-Wall Bracing | 6/2/2020 | 6/2/2020 | 6/2/2020 | P | PART |
Tell Riley
|
|
|
Wall screws Inspection requested via web by Carl Funk//interior gyp shear wall//ok to cover when screws have been added at blocking lines on each floor as discussed//screws per details and email from engineer for gyp shear walls//
|
BLD-Energy code compliance | 5/18/2020 | 5/18/2020 | 5/18/2020 | A | PART |
Tell Riley
|
|
|
firewall insulation Inspection requested via web by Carl Funk//fire wall insulation only ok//call for shear on gyp//
|
BLD-Energy code compliance | 5/15/2020 | 5/15/2020 | 5/15/2020 | P | NR |
Tell Riley
|
|
|
Insulation Firewall Phone #: ###-#### Inspection requested via web by Carl Funk//need to fix R21/add R21 in areas noted on walk through//
|
BLD-Framing/Rough-in | 5/7/2020 | 5/8/2020 | 5/8/2020 | A | PEND |
Tell Riley
|
|
|
Fireblocking Inspection requested via web by Carl Funk//fire separation only//corrections made//need rating for ele heater in separation wall(all Units)//pending ele rough//
|
BLD-Framing/Rough-in | 5/7/2020 | 5/7/2020 | 5/7/2020 | A | FAIL |
Tell Riley
|
|
|
Fire blocking firewalls Phone #: ###-#### Inspection requested via web by Carl Funk/framing for fire walls ONLY//add nuts and bolts in areas noted//add studs in areas noted//add fire blocking in areas noted//see details for truss connections at fire walls//complete air seal//
|
BLD-Wall cover | 4/10/2020 | 4/10/2020 | 4/10/2020 | A | CANC |
Tell Riley
|
|
|
Phone #: ###-#### Inspection requested via web by Carl Funk
|
BLD-Wall Bracing | 3/19/2020 | 3/20/2020 | 3/20/2020 | A | PART |
Tell Riley
|
|
|
Inspection requested via web by Carl Funk
|
BLD-Wall Bracing | 3/16/2020 | 3/17/2020 | 3/17/2020 | A | FAIL |
Tell Riley
|
|
|
Phone #: ###-#### Inspection requested via web by Carl Funk//need to add nails, fix hold downs nails//did walk through with carl//add hold downs where needed//
|
BLD-Foundation | 10/18/2019 | 10/18/2019 | 10/18/2019 | P | PART |
Tell Riley
|
|
|
SERGIO- wall foundation inspection Phone #: ###-####//wip//
|
BLD-Footing | 10/17/2019 | 10/17/2019 | 10/17/2019 | P | PART |
Tell Riley
|
|
|
Sergio Phone #: ###-####//ok when bars added for 32" requirement//
|