Information based on query as of Tuesday, May 7, 2024.
Permit Information
Permit NumberFIR18-00106
StatusIssued
Name FIRE SENTRY SYSTEMS
Site Address 190 E BANNOCK ST
Project NameBoise Elevator Addition
Customer Number 
ePlanReviewYes
Description
Public Elevator Phase: Add new interfacing of Fire Alarm and the Upgrade of 3 existing Public Elevators and 2 new Public Elevators. This includes new elevator shaft smoke and heat detectors, elevator mechanical room mods as shown on drawings, and 2 new RTU's, and smoke damper. Note: New Recall, Alt Recall, Fire Hat, Shunt trip control voltage monitors included. Relocate existing heat detectors as required. There are no NAC modifications. THis work is associated with building permit BLD17-00066.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/17/201910/18/201910/21/2019APART
DetailsTroy Cobbley
A life safety temp for the use of the two elevators is being given with boise fire permission with the states acceptance. The acceptance paperwork is attached to this permit. Per dicussion with Jim Shilton these elvators will still need to be re-inspected by the fire code inspector prior to a final sign off as discussed.

Phone #: ###-#### Inspection requested via web by Jim Shilton
INSP-Final Inspection10/16/201910/17/201910/17/2019AFAIL
DetailsTroy Cobbley
I witnessed the testing of the two heat detectors on the elevator penthouse, as marked on the plans, and they shunt the two elevators. I witnessed the penthouse smoke detector recall the eelvator to the 1st floor. We then went to the 9th floor and tripped the elevator lobby detector and the elevator did nothing and actually continued to function as normal.. Testing was stopped.

Please call me prior to arrival so we can prepare. State Elevator Inspector will make provisions to allow city to inspect permitted 2 new elevators.

Phone #: ###-#### Inspection requested via web by Jim Shilton
INSP-Final Inspection10/15/201910/16/201910/16/2019ACANC
DetailsTroy Cobbley
Call before please
Thanks,
Jim
###-#### Phone #: ###-#### >> Inspection requested via web by Jim Shilton Inspection cancelled from web by: Jim Shilton
INSP-Final Inspection7/16/20187/17/20187/16/2018ACANC
DetailsJim Page
Chris Siewert - Technician Phone #: ###-#### >> Inspection requested via web by John Siewert Inspection cancelled from web by: John Siewert