INSP-Final Inspection | 4/6/2019 | 4/8/2019 | 4/8/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire alarm inspection complete.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 2/13/2019 | 2/14/2019 | 2/14/2019 | A | FAIL |
Troy Cobbley
|
|
|
The hvac units did not shut down upon alarm activation as required per IMC 606.4, need the enclosure for the communicator installed.
As early as possible Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
|
FIR-Aging Inspection | 2/13/2019 | 2/13/2019 | 2/13/2019 | A | FAIL |
Troy Cobbley
|
|
|
Not ready for final due to issues with hvac activation, need protecive cover for IP DACT, need cut sheet for FACP showing internal mounting for IP DACT, need fuel verification for generator, need to verify as-builts are correct (NAC's)
|
INSP-Final Inspection | 2/12/2019 | 2/13/2019 | 2/13/2019 | A | CANC |
Troy Cobbley
|
|
|
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Wednesday, February 13, 2019.
|
INSP-Final Inspection | 2/4/2019 | 2/7/2019 | 2/7/2019 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 1/24/2019 | 1/31/2019 | 1/31/2019 | A | FAIL |
Troy Cobbley
|
|
|
Todays inspection included verifying candellas for the audio/visuals, fire sprinkler risers and smoke detector door release. We were unable to test hvac shutdown due to Target Policy. Plan modifications are required showing the changes strobes, NAC panels, addressing and means of communication. Note IP DACT is installed inproperly and not shown on the plans or battery calcs.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 1/21/2019 | 1/24/2019 | 1/24/2019 | A | DONE |
Troy Cobbley
|
|
|
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price.
3:30 pm test is too late for Target. Nathan cancelled.
|
INSP-Final Inspection | 1/21/2019 | 1/22/2019 | 1/21/2019 | A | CANC |
Troy Cobbley
|
|
|
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, January 21, 2019.
|
INSP-Final Inspection | 11/26/2018 | 11/27/2018 | 11/27/2018 | A | FAIL |
Troy Cobbley
|
|
|
Todays inspection was just for the notification devices. See the city approved plans for the devices overspaced or mounted too high. Not all of the devices have been checked for the correct candella. Contractor will need to contact plan review on whether a plan mod is needed or just as-builts. Also the fire doors did not close when the smoke detectors were tested.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Conference | 9/26/2018 | 9/27/2018 | 9/27/2018 | A | DONE |
Troy Cobbley
|
|
|
We dicussed obstructions to the strobes in the Store Room areas.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|