Permit Information
Permit NumberFIR18-00718
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 1510 N 13TH ST
Project NameHyde Park Hotel - Renovation
Customer Number 
ePlanReviewYes
Description
(Original Submittal) - T.F.S. Has been contracted to submit plans for an existing job that was designed and approved in 2007 for American Fire Protection. FIR07-00315. Plans show existing Fire Sprinkler System with Asbuilts that were done. T.F.S. to added one head in combustible canopy with heat trace to protect it from Freezing. T.F.S. also to installed heads that were never installed on second floor to finish off project.
(NEW) - Project is being Resubmitted for Final approval and inspection.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/8/20191/9/20191/9/2019APASS
DetailsJim Page
Previously noted items have been corrected, fire sprinkler inspection for core and shell only complete.

please call chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection1/8/20191/9/20191/8/2019PCANC
DetailsJim Page
please call Chris ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
INSP-Final Inspection1/4/20191/8/20191/8/2019PFAIL
DetailsJim Page
Flow switches on levels 1 and 2 go instantly to alarm with water flow, flow switches will need to be replaced. Basement level flow switch would not trip with a consistant time, recommend replacement of switch for basement level. PIV took 12 turns to report to panel, needs to be 2 1/2 turns or less.

Please call chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection1/4/20191/7/20191/4/2019PCANC
DetailsJim Page
please call chris ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
INSP-Final Inspection11/14/201811/15/201811/14/2018PCANC
DetailsJim Page
Please call Chris Ford Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
INSP-Sprinkler Rough-in10/25/201810/25/201810/25/2018PPASS
DetailsJim Page
Core and shell fire sprinkler protection rough in inspection complete, overhead fire sprinkler piping above hardlid areas approved for cover.
INSP-Sprinkler Rough-in/Hydro10/24/201810/25/201810/25/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping, remote FDC and undergorund supply complete, no pressure loss observed.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection10/23/201810/24/201810/24/2018PFAIL
DetailsJim Page
Need to re-hydro overhead fire sprinkler piping due to past freeze issues. Cannot find notes on underground and remote FDC hydro, need to perform hydrostatic test on all associated fire sprinkler componenets before final can be completed. Make corrections in discussed locations.

Can we please have the fire alarm inspection as well FIr18-00777. this permit is not showing up online Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection10/23/201810/24/201810/23/2018ACANC
DetailsJim Page
Can we please have the fire alarm inspection as well FIr18-00777. this permit is not showing up online Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
INSP-Final Inspection10/23/201810/25/201810/23/2018ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell