INSP-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Previous correction notes have been addressed and plan mods received.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 | A | FAIL |
Jim Page
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah.
Numerous strobes at wrong height.One Visible coverage is inadequate at speaker SP1:30 in Kitchen. 15cd strobe PS:11:4:5 at vending brown bag needs to be removed. Adjust 11:4:1 to compensate. Its blocked by Refers. Strobes too low and/or blocked by shelves are 10:2:1, 10:2:210:1:4 and 20:2:4. All other equipment tested ok. Audible and visible needs to be retested.
|
INSP-Sprinkler Rough-in/Hydro | 3/4/2019 | 3/5/2019 | 3/4/2019 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Monday, March 04, 2019.
|
INSP-Alarm Testing | 2/22/2019 | 2/25/2019 | 2/25/2019 | A | PART |
Jim Page
|
|
|
Alarm testing for phase 4 and 5 areas complete, city approved drawings must be current for next inspection.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Sprinkler Rough-in/Hydro | 2/22/2019 | 2/25/2019 | 2/22/2019 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese Inspection cancelled via mobile web on Friday, February 22, 2019.
|
INSP-Alarm Testing | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | FAIL |
Troy Cobbley
|
|
|
I was only able to check the sync of the devices today due to multiple a/v's that are overspaced. Plan modifications are required showing all of the changes required today and all of the changes that have been made on prior inspections. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Alarm Testing | 1/17/2019 | 1/18/2019 | 1/18/2019 | A | PART |
Jim Page
|
|
|
Fire alarm testing for TCO requested area in kitchen serving area complete.
As early as possible Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
|
INSP-Alarm Testing | 1/14/2019 | 1/15/2019 | 1/15/2019 | A | DONE |
Jim Page
|
|
|
Fire alarm testing for TCO requested area of cafeteria complete, horn strobes are in place, speaker strobes to be installed for final inspection.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
INSP-Sprinkler Rough-in/Hydro | 1/14/2019 | 1/15/2019 | 1/14/2019 | A | CANC |
Troy Cobbley
|
|
|
As early as possible Phone #: 2088996072 >> Inspection requested via mobile web by Josiah Froese Inspection cancelled via mobile web on Monday, January 14, 2019.
|
INSP-Alarm Testing | 1/14/2019 | 1/14/2019 | 1/14/2019 | P | CANC |
Troy Cobbley
|
|
|
As late as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese Inspection cancelled via mobile web on Monday, January 14, 2019.
|
INSP-Final Inspection | 11/21/2018 | 11/21/2018 | 11/21/2018 | P | PART |
Jim Page
|
|
|
Temporary notification has been placed in areas associated with phase 2, each phase will require a fire alarm inspection for audio visual notification before TCO authorization. Temp A/V devices for phase 2 complete and operational.
|
INSP-Final Inspection | 11/21/2018 | 11/21/2018 | 11/21/2018 | A | FAIL |
Jim Page
|
|
|
Could not sound off audio visual devices due to lack of coordination with micron, inspection will need to be rescheduled.
|
INSP-Conference | 11/20/2018 | 11/21/2018 | 11/21/2018 | A | DONE |
Jim Page
|
|
|
Conference complete.
Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
|
INSP-Alarm Testing | 11/20/2018 | 11/20/2018 | 11/20/2018 | A | CANC |
Jim Page
|
|
|
Spoke with permit holding contractor, Micron needs more of a notice for fire alarm testing, alarm testing cannot be completed today based on conversation with Apex. This request is cancelled by request.
Call prior to going Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
|