Permit Information
Permit NumberFIR19-00059
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION SE
Site Address 9333 W CORY LN
Project NameAventura West Bldg B
Customer Number 
ePlanReviewYes
Description
Install new wet pipe fire sprinkler system beginning at one foot above the floor in the mechanical room.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/29/20198/29/20198/29/2019PPASS
DetailsTroy Cobbley
Permit finaled. Nick Phone #: ###-####
INSP-Final Inspection8/21/20198/22/20198/22/2019PFAIL
DetailsTroy Cobbley
Need insulation and cover inspection for the piping in the storage closets.

Nick Phone #: ###-#### (change inspection to this afternoon, 8-22, per kristin dolan)
INSP-Final Inspection8/12/20198/12/20198/12/2019PFAIL
DetailsJim Page
Provide freeze protection for fire sprinkler piping in storage closets. Storage closets have exposed CPVC, exposed CPVC is not allowed per manufacture specs. Provide signage for FDC bell as required.

Kristin Phone #: ###-####
INSP-Sprinkler Rough-in5/6/20195/6/20195/6/2019PPASS
DetailsTroy Cobbley
Rough-in passed. Tenting passed. Piping can be covered. The wet pipe in the exterior closets will need addressed as per previous conversations.

###-#### Nick
INSP-Sprinkler Rough-in/Hydro4/29/20194/30/20194/30/2019APASS
DetailsTroy Cobbley
The overhead hydro test was witnessed with no visible loss at the guage. Todd Phone #: ###-####
INSP-Supply line flush4/25/20194/26/20194/26/2019APASS
DetailsTroy Cobbley
Underground flush witnessed

Call ahead // Nick Phone #: ###-####