Information based on query as of Friday, May 10, 2024.
Permit Information
Permit NumberFIR19-00127
StatusFinaled
Name PROTEX
Site Address 3101 N SYCAMORE DR
Project NameBoise Fire Station #9
Customer Number 
ePlanReviewYes
Description
Install new code compliant fire alarm system. This work is associated with building permit BLD18-02497.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/201910/17/201910/17/2019APASS
DetailsTroy Cobbley
Permit finaled.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection10/16/201910/16/201910/16/2019PCANC
DetailsTroy Cobbley
To be rescheduled due to time constraints due to work load. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection10/14/201910/15/201910/15/2019PFAIL
DetailsJim Page
Fire sprinkler, fire alarm and fire alarm communicator trades need to be coordinated together to complete this inspection. Provide a record of testing from the monitoring service as discussed. Smoke detector in dayroom is over 23 feet from corner, relocate for code compliance. Provide fan shutdown on large ceiling fan on appuratus floor. Fire alarm system is an engineered system, a resubmittal for plan mod is required to show the addition of the smoke detector in the captians quarters and the addition of the fan shutdown relay. No devices were tested and monitoring was not verified.


Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten