Information based on query as of Friday, May 10, 2024.
Permit Information
Permit NumberFIR19-00254
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 3670 W QUAIL HOLLOW CT
Project NameCROWLEY RESIDENCE
Customer Number 
ePlanReviewYes
Description
THORPE FIRE SPRINKLER SYSTEMS TO INSTALL NEW NFPA 13D FIRE SPRINKLER SYSTEM IN NEW SINGLE FAMILY DWELLING
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/22/201910/23/201910/23/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection is complete.

Backflow test is scheduled to be complete by noon. Please call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection10/21/201910/22/201910/22/2019AFAIL
DetailsJim Page
Provide annual inspection for backflow. Irrigation shutdown on flow switch activation not hooked up coorectly at time of inspection, no flow test completed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in8/12/20198/13/20198/13/2019APASS
DetailsJim Page
Correctionhas been made, approved for cover.

Call James for more info. Tenting re-inspection at entry due to proximity of pipe to exterior deck above. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in8/8/20198/8/20198/8/2019PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
INSP-Sprinkler Rough-in/Hydro8/8/20198/8/20198/8/2019PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed at 200PSI, above the static city pressure requirement, no pressure loss observed.

Overhead rough/hydro and tenting. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello