INSP-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.
Contact Hunter Anderson - ###-#### Final Insp - Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 12/16/2019 | 12/23/2019 | 12/16/2019 | P | CANC |
Jim Page
|
|
|
Contact Hunter Anderson ###-#### 30 min prior to Final Insp Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Final Inspection | 12/16/2019 | 12/17/2019 | 12/16/2019 | P | CANC |
Jim Page
|
|
|
Contact Hunter Anderson ###-#### 30 min prior to Final Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Final Inspection | 12/12/2019 | 12/13/2019 | 12/13/2019 | A | FAIL |
Jim Page
|
|
|
2 pendant heads to close to registers, lees than 12 inches and 155 degree heads are placed. Head that was aded in juicer area is 3 5/8 inches off of wall, a minimum of 4 inches is required. Upright heads next to vetstibule entrance, northside are overspaced, upright heads are 10 on center, upright is 7 foot off of new wall and upright that was added is more than 5 foor off edge of new wall corner.
Contact Hunter Anderson ###-#### 30 min prior to Final Insp. start please, Hunter would like to sched. for early AM as possible.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 12/5/2019 | 12/6/2019 | 12/6/2019 | A | PASS |
Jim Page
|
|
|
Rough to cover inspection for area of work complete, 3 hangers to be relocated due to incorrect install, hangers are in prep/employee only area, north side above ceiling grid. Will verify hanger correction during next inspection request, cover is approved.
Contact Fred Silva ###-#### 30 min prior to RTC Insp. start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 11/25/2019 | 11/26/2019 | 11/26/2019 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping above serving line hardlid is complete, serving line hardlid approved for cover.
Contact Hunter Anderson 208###-#### 30 min prior to Hard Lid insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|