Information based on query as of Sunday, May 5, 2024.
Permit Information
Permit NumberMEC19-05489
StatusFinaled
Name CUSTOM HEATING AND AIR CONDITIONING
Site Address 11539 W FLORIDA DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: complete hvac installation with gas piping for range, water heater and furnace
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/2/20203/3/20203/3/2020PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Dave Sorensen- final ok
Final3/1/20203/2/20203/2/2020AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Dave Sorensen
1- need city approved man j onsite none found
2- need locking caps on a/c service ports
3- need to complete duct blast test and have paper work onsite
Pressure Test12/11/201912/12/201912/12/2019APASS
DetailsBrian Scoles
60lb test on gas supply piping to aud. Gas reg installed inside of building in attic on west side of Aud. Phone #: ###-#### Inspection requested via web by Dave Sorensen- 60lb gas pass from meter underground to regulator in building attic- tagged this gas line at meter- ok to cover
Rough-in12/12/201912/12/201912/12/2019APASS
DetailsBrian Scoles
60lb test on gas supply piping to aud. Gas reg installed inside of building in attic on west side of Aud. Phone #: ###-#### Inspection requested via web by Dave Sorensen- R/I ok- regulator installed in attic
Rough-in12/11/201912/11/201912/11/2019PPART
DetailsBrian Scoles
Rough in inspection on duct system - manuals on site - will be testing gas supply line to aud to 60llbs at a later date. Phone #: ###-#### Inspection requested via web by Dave Sorensen- R/I will pass once regulator is installed in attic and inspected- ok to cover walls only at this time- check equipment at final not set on R/I- still need 60lb gas test witnessed when ready- will need duct blast and air balance at final
Rough-in12/5/201912/6/201912/6/2019PFAIL
DetailsChad Schwendiman
gas pressure and flue test also Phone #: ###-#### Inspection requested via web by Dave Sorensen - No approved manual J onsite. Gas piping from house to ADU is undersized. Need to increase pipe size or increase gas pressure. If choice is to increase gas pressure all piping from meter to regulators will need to be test at 60lbs on a 100lb gauge.
Pressure Test12/6/201912/6/201912/6/2019PPART
DetailsChad Schwendiman
gas pressure and flue test also Phone #: ###-#### Inspection requested via web by Dave Sorensen - 5lb flue pass, 20lb gas pass for piping inside of ADU. Gas piping from house to ADU is undersized. Need to increase pipe size or increase gas pressure. If choice is to increase gas pressure all piping from meter to regulators will need to be test at 60lbs on a 100lb gauge.